Floor loading for servers
with
Internal Battery Feature
Example
#
'a' (sides)
mm (in)
'b' (front)
mm (in)
'c' (rear)
mm (in)
Floor Load
kg/m
2
(lbs/ft
2
)
1
25 (1.0)
254 (10.0)
254 (10.0)
741.7 (151.9)
2
25 (1.0)
508 (20.0)
508 (20.0)
604.1 (123.7)
3
25 (1.0)
762 (30.0)
762 (30.0)
516.6 (105.8)
4
254 (10.0)
254 (10.0)
254 (10.0)
516.4 (105.4)
5
254 (10.0)
508 (20.0)
508 (20.0)
428.8 (87.8)
6
254 (10.0)
762 (30.0)
762 (30.0)
373.1 (76.4)
7
508 (20.0)
254 (10.0)
254 (10.0)
402.9 (82.5)
8
508 (20.0)
508 (20.0)
508 (20.0)
340.6 (69.8)
9
508 (20.0)
762 (30.0)
762 (30.0)
300.9 (61.6)
10
762 (30.0)
254 (10.0)
254 (10.0)
340.1 (69.7)
11
762 (30.0)
508 (20.0)
508 (20.0)
291.7 (59.8)
12
762 (30.0)
762 (30.0)
762 (30.0)
260.9 (53.4)
All measurements are taken from the outside edge of the machine frame, without
covers, unless specifically described otherwise.
Minimum weight distribution is shown in the shaded area of Figure 1 on page 25.
v
“a” = side dimension
v
“b” = front dimension
v
“c” = rear dimension
Weight distribution and multiple systems
Under typical conditions, service clearances of adjacent products may be
overlapped but weight distribution areas should not be overlapped. If weight
distribution clearances are overlapped, the customer should obtain the services of a
qualified consultant or structural engineer to determine floor loading. Regardless of
floor loading, minimum service and aisle clearances must be observed:
v
Rear dimension “d” is
991 mm (39 in.)
.
v
Front dimension “e” is
1168 mm (46 in.).
v
Both “d” and “e” are measured from the frame edge (without covers) to the
nearest obstacle.
v
Cover opening dimensions are also shown.
Note that aisle clearances are not the same between rows of front-facing and
rear-facing covers. Front-facing rows require
1168 mm (46 in.)
of clearance while
rear-facing rows need a
minimum
of
991 mm (39 in.).
Level 03c, May 2011
24
z10 BC IMPP
Содержание Z10 BUISNESS CLASS Z10 BC
Страница 1: ...System z10 Business Class Installation Manual for Physical Planning GC28 6875 03 Level 03c May 2011...
Страница 2: ......
Страница 3: ...System z10 Business Class Installation Manual for Physical Planning GC28 6875 03 Level 03c May 2011...
Страница 8: ...Level 03c May 2011 vi z10 BC IMPP...
Страница 10: ...Level 03c May 2011 viii z10 BC IMPP...
Страница 44: ...Level 03c May 2011 32 z10 BC IMPP...
Страница 50: ...Level 03c May 2011 38 z10 BC IMPP...
Страница 62: ...Level 03c May 2011 50 z10 BC IMPP...
Страница 86: ...LC Duplex Connectors ISC 3 Links ISC 3 Links FC 18 02 ISC 3 Level 03c May 2011 74 z10 BC IMPP...
Страница 106: ...Level 03c May 2011 94 z10 BC IMPP...
Страница 110: ...Level 03c May 2011 98 z10 BC IMPP...
Страница 112: ...Level 03c May 2011 100 z10 BC IMPP...
Страница 116: ...Level 03c May 2011 104 z10 BC IMPP...
Страница 130: ...Level 03c May 2011 118 z10 BC IMPP...
Страница 131: ......
Страница 132: ...Level 03c May 2011 Printed in USA GC28 6875 03...