Grounding specifications
Every three-phase circuit must contain three-phase conductors and an insulated
equipment-grounding conductor. Every single-phase 120 volt branch circuit (used
for the Hardware Management Console and service outlets) must contain one
phase conductor, a neutral conductor, and an insulated equipment-grounding
conductor.
For 200 VAC through 240 VAC installations worldwide, the equipment-grounding
conductor must match local electrical codes and must be green with or without one
or more yellow stripes on the insulation. IBM recommends that the ground wire be
the same size as the phase conductor wires.
Conduit must not be used as the only grounding means. However, any conduit or
cable shield must be connected at both ends in such a way that it is included in the
grounding path in parallel with the grounding conductor it contains. Most electrical
codes require that branch circuit wiring be located in metallic conduit, or be made
from shielded cable, if located under a raised floor. Even when not required by local
regulations, some form of shield around the branch circuit wiring is strongly
recommended as a means of reducing coupling of high-frequency electrical noise
into signal and control cables.
There is information about additional recommendations and requirements for
equipment grounding on IBM's
Resource Link
Web site (http://www.ibm.com/
servers/resourcelink). See "
General Information for Planning a Physical Site
".
Level 03c, May 2011
46
z10 BC IMPP
Содержание Z10 BUISNESS CLASS Z10 BC
Страница 1: ...System z10 Business Class Installation Manual for Physical Planning GC28 6875 03 Level 03c May 2011...
Страница 2: ......
Страница 3: ...System z10 Business Class Installation Manual for Physical Planning GC28 6875 03 Level 03c May 2011...
Страница 8: ...Level 03c May 2011 vi z10 BC IMPP...
Страница 10: ...Level 03c May 2011 viii z10 BC IMPP...
Страница 44: ...Level 03c May 2011 32 z10 BC IMPP...
Страница 50: ...Level 03c May 2011 38 z10 BC IMPP...
Страница 62: ...Level 03c May 2011 50 z10 BC IMPP...
Страница 86: ...LC Duplex Connectors ISC 3 Links ISC 3 Links FC 18 02 ISC 3 Level 03c May 2011 74 z10 BC IMPP...
Страница 106: ...Level 03c May 2011 94 z10 BC IMPP...
Страница 110: ...Level 03c May 2011 98 z10 BC IMPP...
Страница 112: ...Level 03c May 2011 100 z10 BC IMPP...
Страница 116: ...Level 03c May 2011 104 z10 BC IMPP...
Страница 130: ...Level 03c May 2011 118 z10 BC IMPP...
Страница 131: ......
Страница 132: ...Level 03c May 2011 Printed in USA GC28 6875 03...