v
Defective
circuitry
in
the
power
supply
v
Blocked
air
vent
v
Failure
in
other
devices
installed
in
the
cabinet
If
the
internal
temperature
rises
above
70°
C
(158°
F),
one
or
both
power
supplies
automatically
shut
down.
If
one
power
supply
shuts
down,
the
DS4000
Storage
Manager
client
software
displays
a
Needs
Attention
status
in
the
Subsystem
Management
window,
the
alarm
sounds
(if
enabled),
and
the
Overall
DS4800
Configuration
Needs
Attention
LED
on
the
front
bezel
of
the
storage
subsystem
turns
on.
If
a
common
environmental
stress
causes
both
power
supplies
to
shut
down,
the
storage
subsystem
shuts
down,
and
the
DS4000
Storage
Manager
client
software
displays
a
Not
Responding
status
in
the
Subsystem
Management
window.
If
event
monitoring
is
enabled
and
event
notification
is
configured,
the
software
also
issues
critical
event
notifications.
v
Nominal
temperature
exceeded
–
The
storage
subsystem
temperature
exceeds
the
normal
operating
range.
v
Maximum
temperature
exceeded
–
The
storage
subsystem
temperature
exceeds
70°
C
(158°
F).
Use
the
following
procedure
to
resume
normal
operation
after
a
power
supply
shutdown.
Attention:
Power
supplies
automatically
shut
down
when
air
temperature
inside
the
cabinet
reaches
70°
C
(158°
F)
or
above.
If
the
power
supplies
have
shut
down,
immediately
remove
all
cabinet
panels
to
help
cool
the
cabinet
air
temperature
and
prevent
damage
to
the
storage
subsystem.
Note:
If
both
power
supply
and
fan
units
have
shut
down,
start
with
step
below.
1.
If
applicable,
turn
off
the
alarm.
2.
Use
the
DS4000
Storage
Manager
client
software
to
a
storage
subsystem
profile.
3.
In
the
DS4000
Storage
Manager
client
Subsystem
Management
window,
select
Advanced
Troubleshooting
View
Event
Log
to
display
the
DS4800
critical
events.
Look
for
one
of
the
following
critical
event
entries:
v
Event
281B
-
Nominal
temperature
exceeded
v
Event
281C-
Maximum
temperature
exceeded
4.
Try
alleviating
the
overheating
problem
by
doing
the
following:
v
Removing
all
panels
from
the
cabinet.
v
Cooling
the
area
using
external
fans.
v
Shutting
down
the
power
to
the
storage
subsystem
or
storage
expansion
enclosures
(Follow
the
power-down
procedure
described
in
5.
Stop
all
I/O
activity
to
the
storage
subsystem
and
to
all
attached
storage
expansion
enclosures.
6.
Wait
until
the
ambient
air
temperature
around
the
storage
subsystem
cools.
The
storage
subsystem
is
capable
of
power-up
recovery
without
operator
intervention
after
the
temperature
inside
the
power
supply
and
fan
unit
cools
to
below
70°
C
(158°
F).
After
the
air
has
cooled,
the
power
supplies
should
turn
on
automatically.
If
the
power
supplies
restart
automatically,
the
controllers
reset
and
return
to
normal
operation.
130
IBM
System
Storage
DS4800
Storage
Subsystem:
Installation,
User’s,
and
Maintenance
Guide
Содержание TotalStorage DS4800
Страница 1: ...IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide GC26 7845 01...
Страница 2: ......
Страница 3: ...IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide GC26 7845 01...
Страница 18: ...xvi IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Страница 168: ...140 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Страница 216: ...188 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Страница 220: ...192 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Страница 240: ...212 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Страница 246: ...218 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Страница 249: ......
Страница 250: ...Part Number 22R6614 Printed in USA GC26 7845 01 1P P N 22R6614...