Checkout procedure
The checkout procedure is the sequence of tasks that you should follow to
diagnose a problem in the server.
About the checkout procedure
Before you perform the checkout procedure for diagnosing hardware problems,
review the following information:
v
Read the safety information that begins on page “Safety” on page vii.
v
IBM Dynamic System Analysis (DSA) provides the primary methods of testing
the major components of the server, such as the system board, Ethernet
controller, keyboard, mouse (pointing device), serial ports, and hard disk drives.
You can also use them to test some external devices. If you are not sure whether
a problem is caused by the hardware or by the software, you can use the
diagnostic programs to confirm that the hardware is working correctly.
v
When you run DSA, a single problem might cause more than one error message.
When this happens, correct the cause of the first error message. The other error
messages usually will not occur the next time you run DSA.
Exception:
If multiple error codes or light path diagnostics LEDs indicate a
microprocessor error, the error might be in the microprocessor or in the
microprocessor socket. See “Microprocessor problems” on page 181 for
information about diagnosing microprocessor problems.
v
Before you run diagnostic programs, you must determine whether the failing
server is part of a shared hard disk drive cluster (two or more servers sharing
external storage devices). If it is part of a cluster, you can run all diagnostic
programs except the ones that test the storage unit (that is, a hard disk drive in
the storage unit) or the storage adapter that is attached to the storage unit. The
failing server might be part of a cluster if any of the following conditions is true:
– You have identified the failing server as part of a cluster (two or more servers
sharing external storage devices).
– One or more external storage units are attached to the failing server and at
least one of the attached storage units is also attached to another server or
unidentifiable device.
– One or more servers are located near the failing server.
Important:
If the server is part of a shared hard disk drive cluster, run one test
at a time. Do not run any suite of tests, such as “quick” or “normal” tests,
because this might enable the hard disk drive diagnostic tests.
v
If the server is halted and a POST error code is displayed, see Appendix A,
“UEFI/POST error codes,” on page 297. If the server is halted and no error
message is displayed, see “Troubleshooting by symptom” on page 173 and
“Solving undetermined problems” on page 189.
v
For information about power-supply problems, see “Solving power problems”
on page 187 and “Power-supply LEDs” on page 164.
v
For intermittent problems, check the event log; see “Event logs” on page 166 and
Appendix C, “DSA messages,” on page 321.
152
System x3750 M4 Types 8722 and 8733: Installation and Service Guide
Содержание System x3750 M4 Type 8733
Страница 1: ...System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 2: ......
Страница 3: ...System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 138: ...122 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 164: ...148 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 210: ...194 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 220: ...204 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 303: ...SAS cable guide Adapter SAS signal cable Chapter 6 Removing and replacing components 287...
Страница 304: ...8x2 5 inch backplane and adapter 288 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 305: ...Cabling the combination power configuration cable to the backplanes Chapter 6 Removing and replacing components 289...
Страница 306: ...4x2 5 inch backplane 290 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 308: ...8x2 5 inch backplane 292 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 310: ...294 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 312: ...296 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 332: ...316 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 672: ...656 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 676: ...660 System x3750 M4 Types 8722 and 8733 Installation and Service Guide...
Страница 693: ......
Страница 694: ...Part Number 90Y4479 Printed in USA 1P P N 90Y4479...