Install SCM
To install a SCM, complete the following steps:
1.
When the node being serviced is above EIA location 29U, the ladders must be used while
installing or removing the rear and front FRUs and cables.
2.
Perform the following procedure on ONLY THE FRU(s) BEING SERVICED. The following images
are generic and do not represent the literal location being serviced.
3.
Modifying FRU locations which are not called out for service can have adverse effects on the
system, INCLUDING SYSTEM OUTAGE AND LOSS OF DATA.
4.
The torque tool (P/N 41V1059) is required for this procedure. The torque tool was initially shipped
with the system.
5.
CAUTION: If the system slide rails are installed above EIA location 29U, two Support Services
Representatives (SSRs) must perform the procedure together and the following equipment must be
used as a safety precaution for servicing: ServerLIFT tool (P/N 74Y4399), two Hard hats (P/N
5442867) and two service-qualified ladders (P/N 46G5947 and P/N 00E4866)
CAUTION:
Do not allow dust or debris to get into the processor slot. Extraneous material on the processor seat
can have adverse effects on the system, INCLUDING SYSTEM OUTAGE.
1.
This step only applies if you are not replacing an existing SCM.
Determine whether the processor
lid covers one processor socket (A) or two processor sockets (B). If the lid covers one processor
socket, go to step 2 and skip step 3. If the lid covers two processor sockets, skip step 2 and follow
step 3.
2.
This step only applies if you are not replacing an existing SCM.
If the processor socket has a
single processor lid, remove the processor lid.
a.
© Copyright IBM Corp. 2014
19