Table 23. Sensor information, event description, and service action for the 8348-21C (continued)
Sensor name (Sensor ID)
Event description
Service action
FW Boot Progress (0x05)
v
System Firmware Error
v
System Firmware Hang
SEL events with OEM record c0 |
000e000 | 3a150
xxxxxxx indicate that
a boot failed. Search for boot failure
SEL events that have a time stamp in
close proximity to the time stamp of
this SEL event. If events exist, go to
“Resolving a system firmware boot
failure” on page 4.
System Firmware Progress
No service action is required.
OCC Active (0x08)
Device Disabled
Replace the system processor. Go to
“8348-21C locations” on page 133 to
identify the physical location and
removal and replacement procedure.
v
State Deasserted
v
Device Enabled
No service action is required.
Ambient Temp (0x0A)
v
Upper Critical - going low
v
Lower Non-critical – going low
v
Lower Non-critical – going high
v
Lower Critical – going high
v
Lower Non-recoverable – going
low
v
Lower Non-recoverable – going
high
v
Upper Non-critical – going low
v
Upper Non-critical – going high
v
Lower Critical - going low
v
Upper Non-recoverable – going
low
v
Upper Non-recoverable – going
high
No service action is required.
Upper Critical - going high
Ensure that the room temperature
meets the requirements that are
specified for the system. Ensure that
no obstructions are blocking air flow
to the system.
80
Problem analysis, system parts, and locations for the 8335-GCA, 8335-GTA, 8335-GTB, and 8348-21C
Содержание Power System 8335-GCA
Страница 2: ......
Страница 16: ...xiv Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 133: ...System parts Figure 6 System parts Finding parts and locations 117 ...
Страница 160: ...144 Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 172: ...156 Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 173: ......
Страница 174: ...IBM ...