Table 21. Sensor information, event description, and service action for the 8335-GCA and 8335-GTA (continued)
Sensor name (Sensor ID)
Event description
Service action
All PGood (0x1C)
v
Interlock Power Down
v
Power Off Power Down
v
Power Cycle
v
240VA Power Down
No service action is required.
v
AC Lost
v
Soft Power Control Failure
v
Ensure that ac power is supplied
to the rack.
v
Ensure that the system power
cords are plugged tightly into both
the power supply and the rack
power distribution unit (PDU) for
both system power supplies.
v
Ensure that the system was not
powered off.
v
Power Unit Failure Detected
v
Predictive Failure
v
Ensure that ac power is supplied
to the rack.
v
Ensure that the power supply
cords are plugged tightly into the
power supplies and the rack PDU
unit.
v
Ensure that the system was not
powered off.
v
Check for service action required
SEL events for the power supply
sensor. If any exist, follow the
service action that is specified in
“Identifying a service action by
using sensor and event information
for the 8335-GCA and 8335-GTA”
on page 37.
42
Problem analysis, system parts, and locations for the 8335-GCA, 8335-GTA, 8335-GTB, and 8348-21C
Содержание Power System 8335-GCA
Страница 2: ......
Страница 16: ...xiv Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 133: ...System parts Figure 6 System parts Finding parts and locations 117 ...
Страница 160: ...144 Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 172: ...156 Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 173: ......
Страница 174: ...IBM ...