SRN
FRU List
Problem
2A006
Disk-drive module (90%)
(“Disk Drive Modules” on page 3-17).
Backplane assembly (10%)
(“Front Backplane Assembly” on
page 3-48 or “Back Backplane Assembly”
on page 3-52).
Description: Async code 06 has been received. This code
indicates that a disk drive module has detected the loss of
redundant power or cooling.
Action: Go to “MAP 2021: 7133 – Redundant Power” on
page 2-2021-1 to further isolate the problem.
2A106
Fan-and-power-supply assembly (90%)
(“Fan-and-Power-Supply Assemblies” on
page 3-32).
Power-distribution tray assembly (6%)
(“Power-Distribution Tray Assemblies” on
page 3-38).
Back-power card (2%)
(“Back-Power Cards” on page 3-41).
Backplane assembly (2%)
(“Front Backplane Assembly” on
page 3-48 or “Back Backplane Assembly”
on page 3-52).
Description: Async code 06 has been received. This code
indicates that multiple disk drive modules have detected the loss
of redundant power or cooling.
Action: Go to “MAP 2010: 7133 – START” on page 2-2010-1 to
further isolate the problem.
2A206
Disk drive module (100%)
(“Disk Drive Modules” on page 3-17).
Description: A disk drive module has detected that one of its SSA
links has failed the POSTs.
|
Action: Use the Link Verification service aid (see the chapter
|
about SSA service aids in the SSA Adapters: User’s Guide and
|
Maintenance Information manual) to determine where the SSA
link is broken. Run diagnostics in System Verification mode to
the two disk drive modules that are nearest to, and on each side
of, the place where the link is broken. The diagnostics show
which disk drive module detected the problem.
2FFFF
None
Description: An async code that is not valid has been received.
Action: Go to “Software and Microcode Errors” on page 2-8.
300C0
Disk drive module (90%)
(“Disk Drive Modules” on page 3-17).
Backplane assembly (10%)
(“Front Backplane Assy” on page 3-48 or
“Back Backplane Assy” on page 3-52).
Description: A disk drive module has detected the loss of
redundant power or cooling.
Action: Go to “MAP 2021: 7133 – Redundant Power” on
page 2-2021-1 to further isolate the problem.
301C0
Fan-and-power-supply assembly (90%)
(“Fan-and-Power-Supply Assemblies” on
page 3-32).
Power-distribution tray assembly (6%)
(“Power-Distribution Tray Assemblies” on
page 3-38).
Back-power card (2%)
(“Back-Power Cards” on page 3-41).
Backplane assembly (2%)
(“Front Backplane Assy” on page 3-48 or
“Back Backplane Assy” on page 3-52).
Description: Multiple disk drive modules have detected the loss of
redundant power or cooling.
Action: Go to “MAP 2010: 7133 – START” on page 2-2010-1 to
further isolate the problem.
303FF
Disk drive module (100%)
(“Disk Drive Modules” on page 3-17).
Description: An SCSI status that is not valid has been received.
Action: Go to “Software and Microcode Errors” on page 2-8
before exchanging any FRUs.
|
31000
|
Disk drive module (100%) (“Disk Drive
|
Modules” on page 3-17).
|
Description: The disk drive has been reset by the adapter. The
|
disk drive might be going to fail.
|
Action: If the disk drive can still be accessed, the user should
|
create a backup of all the data from this disk drive, then remove
|
the disk drive from the system configuration. Exchange the FRU
|
for a new FRU.
Chapter 2. Problem Determination Procedures
2-5
Содержание 7133 Series
Страница 1: ...7133 SSA Disk Subsystems Service Guide SY33 0185 02...
Страница 2: ......
Страница 3: ...7133 SSA Disk Subsystems Service Guide SY33 0185 02...
Страница 8: ...vi 7133 Service Guide...
Страница 14: ...xii 7133 Service Guide...
Страница 44: ...Labels Dummy Fan and Power Supply Assembly 1 30 7133 Service Guide...
Страница 94: ...2 10 7133 Service Guide...
Страница 110: ...2 2021 6 7133 Service Guide...
Страница 114: ...2 2022 4 7133 Service Guide...
Страница 138: ...2 2330 18 7133 Service Guide...
Страница 146: ...2 16 7133 Service Guide...
Страница 210: ...3 64 7133 Service Guide...
Страница 222: ...4 12 7133 Service Guide...
Страница 229: ......
Страница 230: ...Part Number 32H6990 Printed in the United Kingdom 32H699 SY33 185 2...