Model D40 in a Netfinity Rack
Step 1. Note: For a translation of the following notice, see the 7133 Serial Disk
Systems and SSA Adapters: Translated Safety Notices manual.
CAUTION:
The stabilizer must be correctly attached to the bottom front of the rack,
or the rack must be firmly fastened to the floor, to prevent the rack from
tipping forward while the 7133 is being installed into the rack. Do not
install or pull out any unit unless either the stabilizer is firmly attached to
the rack, or the rack is firmly fastened to the floor, as described in the
rack installation instructions.
Refer to Figure 132.
Step 2. At the back of the rack, remove the screws
1
and
6
and the washers
2
and
5
.
Step 3. Remove the two back brackets
3
and
4
.
Figure 132. Removing the Back Brackets
Chapter 3. Removal and Replacement Procedures
229
Содержание 7133 D40
Страница 1: ...7133 Models D40 and T40 Serial Disk Systems Service Guide GY33 0192 07 ...
Страница 2: ......
Страница 3: ...7133 Models D40 and T40 Serial Disk Systems Service Guide GY33 0192 07 ...
Страница 10: ...viii 7133 Models D40 and T40 Service Guide ...
Страница 14: ...xii 7133 Models D40 and T40 Service Guide ...
Страница 90: ...72 7133 Models D40 and T40 Service Guide ...
Страница 260: ...Assembly 1 7133 Model D40 242 7133 Models D40 and T40 Service Guide ...
Страница 262: ...Assembly 1 continued 244 7133 Models D40 and T40 Service Guide ...
Страница 264: ...Assembly 1 continued 246 7133 Models D40 and T40 Service Guide ...
Страница 292: ...274 7133 Models D40 and T40 Service Guide ...
Страница 305: ......
Страница 306: ...Part Number 18P6104 Printed in the U S A GY33 0192 07 1P P N 18P6104 ...