3. The pins must be open to keep the UPS running. If the UPS shuts down
because the remote emergency power-off connector pins are shorted, restart
the UPS by reopening the remote emergency power-off connector pins and
turning on the UPS manually. Maximum resistance in the shorted loop is 10
ohm.
4. To avoid accidental load loss, always test the remote emergency power-off
function before you apply your critical load.
To connect a remote emergency power-off switch, complete the following steps:
1. Turn off the UPS, disconnect all external cables, and make sure that the UPS is
disconnected from utility power.
2. Remove the remote emergency power-off connector from the accessory kit.
Note:
Make sure that no jumper is installed in the remote emergency power-off
connector. If a jumper is installed, remove it before you connect to the remote
emergency power-off connector.
12
6000 VA UPS and 6000 VA EBM: Installation and Maintenance Guide
Содержание 6000 VA LCD 4U
Страница 1: ...6000 VA LCD 4U Rack UPS 6000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 2: ......
Страница 3: ...6000 VA LCD 4U Rack UPS 6000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 14: ...xii 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 32: ...18 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 60: ...46 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 70: ...56 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 74: ...60 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 82: ...68 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 86: ...72 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 87: ......
Страница 88: ...Part Number 81Y1032 Printed in USA 1P P N 81Y1032...