Table 14. Typical alarms and conditions (continued)
Alarm or condition
Possible cause
Action
Site Wiring Fault
(Alarm 194)
Fast Beeping Alarm
An alarm is triggered when the
difference between the ground and
neutral voltage is
≥
25 V (tolerance
+50 V, -0 V).
Have a qualified electrician correct
the wiring problem. If the UPS is not
wired with a neutral wire, change the
Site Wiring Fault Alarm
setting to
Disabled
in the
Settings
menu (see
Remote Emergency Power Off
(Alarm 12)
Fast Beeping Alarm
The external contacts in the rear of
the UPS are configured for remote
emergency power-off operation, and
they are activated.
The UPS de-energizes the load and
enters Standby mode. For more
information, see “Installing the remote
emergency power-off” on page 11.
Output Overload
(Notice 25)
Slow Intermittent Alarm
The load level is at or has exceeded
the configurable threshold limit for a
Level 1 Overload condition.
See “Behavior on overload” on page
27.
The UPS can support the load
indefinitely at this load level.
The alarm clears when the load drops
below 5% of the set point.
Output Overload Level 2
(Alarm 159)
Fast Beeping Alarm
The load level is >101% and <110%
of the UPS rating.
See “Behavior on overload” on page
27.
Immediately remove some of the
equipment from the UPS.
The alarm clears when the load drops
below 5% of the set point.
Output Overload Level 3
(Alarm 162)
Fast Beeping Alarm
The load is >110% of the UPS rating.
See “Behavior on overload” on page
27.
Shutdown is imminent.
The alarm clears when the load drops
below 5% of the set point.
Battery DC Over Voltage
(Alarm 68)
Fast Beeping Alarm
The battery voltage levels have
exceeded the maximum allowable
limits.
The UPS turns off the charger until
the next power recycle. Contact your
service representative.
Charger Failure
(Alarm 34)
Continuous Alarm
A battery charger fault has been
detected.
The UPS turns off the charger until
the next power recycle. Contact your
service representative.
Inverter AC Over Voltage
(Alarm 0)
Fast Beeping Alarm
The UPS has detected abnormally
high output voltage levels.
The UPS transfers to Bypass mode if
supporting the load.
Inverter AC Under Voltage
(Alarm 1)
Fast Beeping Alarm
The UPS has detected abnormally
low output voltage levels.
The UPS transfers to Bypass mode if
supporting the load.
Rectifier Input Over Current
(Alarm 26)
Fast Beeping Alarm
The UPS has detected that rectifier
input current limits have been
exceeded.
The UPS transfers to Battery mode if
supporting the load.
Inverter Output Over Current
(Alarm 27)
Fast Beeping Alarm
The UPS has detected that the
inverter output current limits have
been exceeded.
The UPS transfers to Bypass mode if
supporting the load.
DC Link Over Voltage
(Alarm 28)
Fast Beeping Alarm
The link or rail voltage has exceeded
its upper threshold limit.
The UPS transfers to Bypass mode if
supporting the load.
Output Short Circuit
(Alarm 58)
Fast Beeping Alarm
The UPS has detected an abnormally
low impedance placed on its output
and considers it a short circuit.
If the UPS is in Normal mode, the
UPS transfers to Bypass mode if
available, otherwise, the UPS shuts
down after five line cycles.
If the UPS is in Battery mode, the
UPS shuts down after five line cycles.
Chapter 6. Troubleshooting
53
Содержание 6000 VA LCD 4U
Страница 1: ...6000 VA LCD 4U Rack UPS 6000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 2: ......
Страница 3: ...6000 VA LCD 4U Rack UPS 6000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 14: ...xii 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 32: ...18 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 60: ...46 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 70: ...56 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 74: ...60 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 82: ...68 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 86: ...72 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Страница 87: ......
Страница 88: ...Part Number 81Y1032 Printed in USA 1P P N 81Y1032...