Page 19
5. Technical Data
5.1 Raw water requirements regarding water
quality
The system may only be operated with
water that is free of
iron and manganese
.
Water
salinity
must not exceed
750 mg/l
.
Chlorine concentration
in the water must not amount to
greater than
0.1 mg/l
.
If
water
hardness
does not exceed a maximum of
25 °dH
(
12 °dH
KH
), the system may be operated without pretreatment
by a softening device. Otherwise, a softening plant must be
installed upstream in order to replace the calcium and magne-
sium salts contained in the water for neutral salts. Failure to
observe these hints may leed to hardness precipitation and
membrane blocking.
5.2 Raw water requirements regarding pres-
sure
Inlet pressure of the raw water must be
at least 2 bar
and must
not exceed
a maximum of 6 ba
r (inlet pressure is restricted by
the pressure regulator set to 6 bar).
In order to allow for blending the permeate with raw water, inlet
pressure of the raw water must be
1 bar beyond permeate
pressure
. Permeate pressure may be monitored by means of
the PI110.60 pressure gauge.
5.3 Permeate quality
The plant has a desalination rate of 96 to 98 %. As such, per-
meate with a
conductivity from 5 to 20 µS/cm
is produced
from typical drinking water complying with valid drinking water
regulations. In case of water with heavy mineral loading, how-
ever, conductivity may be significantly higher.
Содержание WL-RO-170
Страница 1: ...Reverse osmosis plants WL ROB 170 WL RO 170 WLROB170 ENx WLROB170 EN Manual...
Страница 21: ...Page 21 5 5 Dimension sheet Fig 3 Front Top view Permeate Connection R3 4...
Страница 22: ...Page 22 Fig 4 Lateral view Fig 5 Front view of securing and fixing plate Concentrate Hose 8 Wastewater drain...
Страница 46: ...Seite 46 This page intentionally left blank...