This menu item is for display purposes only. When an
EEXP, EER or VSD Compressor is controlling unit
temperature, the relative position in steps for a stepper
motor driven valve or % running speed for a VSD
compressor is recorded 1 hour after the most recent
defrost. This is stored as a reference value and is used to
control temperature by maintaining this valve position or
compressor motor speed until service can be performed
on the unit. This value is referred to as Step Reference
and is intended for engineering evaluation purposes.
VTYP
This menu item defines the temperature control method
applied. This can consist of electronic evaporator
pressure regulating valves, electronic expansion valves,
on/off control of fixed speed compressors, variable speed
drive control of VSD driven compressors, PWM control
of liquid line solenoids and /or suction stop solenoids.
Depending on the temperature control strategy
employed, a relay module properly connected to the
compressor contactor, solenoids, etc., and /or a
Safe-NET control module is required for temperature
regulating device control functions. See section on
Safe-NET wiring for proper equipment, techniques and
safety considerations.
0-10
This control method utilizes a 0-10VDC output. The
10VDC output is supplied from the control device and is
optically isolated from the Safe-NET power supply. A
Safe-NET control module is required for this mode.
(See section on Safe-NET wiring for proper equipment,
techniques and safety considerations). This control
method is commonly employed on VSD compressors.
CD-16
Stepper motor control for Sporlan CDS-16 — A
Safe-NET control module is required for this mode.
(See section on Safe-NET wiring for proper equipment,
techniques and safety considerations.)
CD-09
Stepper motor control for Sporlan CDS-9 — A
Safe-NET control module Is required for this mode.
(See section on Safe-NET wiring for proper equipment,
techniques and safety considerations).
CD-08
Stepper motor control for Sporlan CDS-8 — A
Safe-NET control module Is required for this mode.
(See section on Safe-NET wiring for proper equipment,
techniques and safety considerations).
4-44
P/N 0461391A
MENUS
SREF
Value
Menu Structure — SREF