VALVE MENU
The Valve menu is used to configure temperature control
output type and operational parameters for units whose
temperature controlling device (compressor, VSD, liquid
solenoid, suction stop solenoid, EEXP, EEPR) is
controlled by the Safe-NET display module. This menu
also contains maintenance functions to allow manual
control of a temperature controlling device for
troubleshooting and repair activity.
A relay module properly connected to the compressor
contactor, solenoids, etc., is required for temperature
regulating device control functions. See section on
Safe-NET wiring for proper equipment, techniques and
safety considerations.
Note:
Changing these parameters (as well as performing
maintenance functions) requires that a valid PASSWORD
be entered first.The section describing the procedure for
entering the PASSWORD is covered in the associated
section of this manual.
4-40
P/N 0461391A
MENUS
VALVE
CLAV
DSVR
DHVR
CSVR
CHVR
C-OF
V0OF
NORL
CLOS
OPEN
VTYP
VPOS
Value
Value
Value
Value
Value
Value
Value
SREF
Menu Structure — VALVE