The Safe-NET system is capable of terminating defrost
activity based on evaporator coil temperature, return air,
or discharge air. When the Safe-NET system is configured
to control defrost, the TSET setting provides a
temperature set point at which to terminate a defrost
cycle. This setting is only effective when defrost
termination is set to TSEN, RAIR or DAIR.
Setting this parameter is done in the DEFROST menu.
After navigating to the TSET submenu item, the display
will cycle between TSET and the current setting. While
the setting is being displayed, press ENTER on the Hand-
Held device or press the SELECT button on the Safe-
NET display module to allow editing of the value. When
the Safe-NET display module begins flashing the value,
use the UP or DOWN arrow keys on the Hand-Held
device or the UP /DOWN buttons on the Safe-NET
display module to change the setting.
Once the desired setting is displayed, press the ENTER
key on the Hand-Held device or the SELECT button on
the Safe-NET display module to store the new value to
NV memory. The display will revert to cycling between
TSET and the new value.
Note:
At least one coil temperature sensor, one discharge air
sensor or one return air sensor must be installed, and
defrost termination must be set to TSEN for this setting to
have an effect.
4-34
P/N 0461391A
MENUS
TSET
Value
–55.0
TSET
–54.0
–53.0
170.0
Menu Structure — TSET