Communication Alarm – “CoM”
If there are no network communication attempts for a
period of more than 30 minutes, the display module sets
a communication alarm and shows it on the display.
When the display module itself is controlling rather than
(dSPn) a network, the Display Number in setup must be
set to “nonE”to prevent alarm generation.
Product High Temperature Alarm – “PrHi”
This alarm will be generated if the product simulator
average is above high alarm set-point for product alarm
delay time
T
HE
P
R
H
I AND
P
R
L
O ALARMS ARE AVAILABLE ONLY IF
PRODUCT SENSORS ARE INSTALLED
.
Product Low Temperature Alarm – “PrLo”
This alarm will be generated if the product simulator
average is below low alarm set-point for product alarm
delay time.
Sectional Faults for
Medium Temperature Impact Cases
with Multiple Coils
A section of the modular coil is above or below the alarm
set point for the period of time set in the programmed
alarm delay
.
Center section of a 12-ft case.
Left-hand section of an 8- or 12-ft case.
Right-hand section of an 8- or 12-ft case.
3-8
P/N 0461391A
ALARMS