ALARMS
A red LED on the board turns on during alarm. The
display will show a four-character word for about 3
seconds alternating with a blank display for 9 seconds.
Following are details of alarms applicable to Self
contained cases.
Alarm with Sensor Number – “SEnS”
This alarm is generated when the control is initialized,
and indicates that the number of sensors entered in the
control is different from the number of sensors connected
to the control. This Alarm can be cleared only by
changing the reading for number of sensors to 0 and
resetting the display module which then updates the
reading to the number of sensors connected. This is
caused by the control not being set up correctly or by a
sensor having failed.
Alarm with Sensor reading – “noSn”
This alarm is generated when the display module is
unable to read the sensors for five consecutive seconds.
This alarm clears automatically when the control is able
to read the sensors. This may be caused by a sensor being
disconnected or shorted. This alarm clears automatically
when the control is able to read the sensors.
Discharge Air High Alarm – “dSHi”
This alarm is generated when the average discharge air
temperature in the case, over the programmed alarm
delay time, is higher than the High Alarm value stored in
the control. This alarm will clear if the average discharge
air temperature goes below the High alarm value.
T
HIS
ALARM IS AVAILABLE ONLY IF DISCHARGE SENSORS ARE
INSTALLED
.
Discharge Air Low Alarm – “dSLo”
This alarm is generated when the average discharge air
temperature in the case, over the programmed alarm
delay time, is lower than the Low Alarm value stored in
the control. This alarm will reset if the average discharge
air temperature goes higher than Low alarm value.
T
HIS ALARM IS AVAILABLE ONLY IF DISCHARGE SENSORS ARE
INSTALLED
.
Note:
Programmable alarm delay (AdLy) is described in
a later section.