HIGH
The HIGH parameter sets the high temperature alarm set
point for the discharge air temperature sensor(s). This set
point and associated alarm is valid for the Safe-NET
system when applied as a Monitoring or Control system.
The configurable range of the HIGH alarm (control set
point) is +16 ºF.
Setting this parameter is done in the SETUP menu. After
navigating to the sub menu item, the display will cycle
between HIGH and the current set point. While the set
point is being displayed, press ENTER on the Hand-Held
device or press the SELECT button on the Safe-NET
display module to allow editing of the value. When the
Safe-NET display module begins flashing the value, use
the UP or DOWN arrow keys on the Hand-Held device or
the UP /DOWN buttons on the Safe-NET display module
to increment or decrement the value to the desired set
point.
Once the desired set point is displayed, press the ENTER
key on the Hand-Held device or the SELECT button on
the Safe-NET display module to store the new value to
NV memory. The display will revert to cycling between
HIGH and the new value.
Note:
The HIGH and LOW alarm settings are limited to +/–
– 16
deg F from product simulator temperature set point. Setting
the product simulator set point will not modify the current
alarm settings.They must be set independently to ensure
proper alarming.
One or more Discharge Air temperature sensors must be
installed in order to enable associated alarm functions.
4-24
P/N 0461391A
MENUS
Menu Structure — HIGH