The ADLY parameter sets the alarm delay in minutes for
the discharge air temperature. In the event that the sensed
temperature of the product simulator exceeds the pre-set
high temperature alarm setting for the discharge air
temperature sensor for a period equal to or greater than
the ADLY setting, the alarm is signaled. This is true for
low temperature alarms as well. There is only one time
delay associated with all discharge air temperature
alarms.
Setting this parameter is done in the SETUP menu. After
navigating to the ADLY sub menu item, the display will
cycle between ADLY and the current setting. While the
setting is being displayed, press ENTER on the Hand-
Held device or press the SELECT button on the
Safe-NET display module to allow editing of the value.
When the Safe-NET display module begins flashing the
value, use the UP or DOWN arrow keys on the Hand-
Held device or the UP /DOWN buttons on the Safe-NET
display module to increment or decrement the value to
the desired setting.
Once the desired setting is displayed, press the ENTER
key on the Hand-Held device or the SELECT button on
the Safe-NET display module to store the new value to
NV memory. The display will revert to cycling between
ADLY and the new value.
Note:
The HIGH and LOW alarm settings are limited to +/–
–16
deg F from set point. Setting the set point will not modify
the current alarm settings.They must be set independently
to ensure proper alarming.
One or more Discharge Air temperature sensors must be
installed in order to enable associated alarm functions.
4-23
P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
Menu Structure — ADLY