3.
Mod
— Modular defrost is selected to support
HUSSMANN medium temperature Impact
™
cases with
modular coils installed. Each 4 foot section of coil
defrosts in sequence up to 28 minutes each hour
(overridden by termination temperature if temperature is
reached before the timer expires).
4.
ELE2
— ELE2-type defrost will terminate the
defrost cycle based on time or termination temperature.
The defrost heaters will de-energize but refrigeration will
not start until a command is received from a master
device. This is done to coordinate restart of refrigeration
after all cases in a system have finished their associated
defrost cycle.
5.
GAS
— Not Available at this time.
6.
ELE1
— ELE1-type defrost will terminate the
defrost cycle based on time or termination temperature.
The defrost heaters will de-energize and refrigeration will
start simultaneously. This type is for stand-alone
operation of low temperature units.
Setting the DTYP parameter is done in the DEFROST
menu. After navigating to the DEFROST submenu item,
the display will cycle between DTYP and the current
setting. While the setting is being displayed, press
ENTER on the Hand-Held device or press the SELECT
button on the Safe-NET display module to allow editing
of the value. When the Safe-NET display module begins
flashing the value, use the UP or DOWN arrow keys on
the Hand-Held device or the UP /DOWN buttons on the
Safe-NET display module to change the setting.
Once the desired setting is displayed, press the ENTER
key on the Hand-Held device or the SELECT button on
the Safe-NET display module to store the new value to
NV memory. The display will revert to cycling between
FSET and the new value.
Note:
A relay module properly connected to defrost heaters,
solenoids, etc., is required for this control function.
4-31
P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
DTYP
DET
ELE2
GAS
ELE1
OffC
Mod
DTYP
New Value
Menu Structure — DTYP