TTYP
The Safe-NET system is capable of terminating defrost
activity based on evaporator coil temperature (TSEN),
return air (RAIR), discharge air (DAIR), time (TIM) or
input from a termination temperature activated switch
(DIGI). When the Safe-NET system is configured to
control defrost, this setting determines which input
parameter is used to terminate a defrost cycle. The DURA
setting is always enabled as a fail-safe defrost duration
time in the event a selected termination input fails. If the
failure is such that defrost termination would occur
immediately, a 10- minute guaranteed defrost cycle
duration is employed.
Setting this parameter is done in the DEFROST menu.
After navigating to the TTYP submenu item, the display
will cycle between TTYP and the current setting. While
the setting is being displayed, press ENTER on the Hand-
Held device or press the SELECT button on the Safe-
NET display module to allow editing of the value. When
the Safe-NET display module begins flashing the value,
use the UP or DOWN arrow keys on the Hand-Held
device or the UP /DOWN buttons on the Safe-NET
display module to change the setting.
Once the desired setting is displayed, press the ENTER
key on the Hand-Held device or the SELECT button on
the Safe-NET display module to store the new value to
NV memory. The display will revert to cycling between
TTYP and the new value.
Note:
The sensed input selected for defrost termination must be
installed and defrost termination set to TSEN for this
feature to operate.
STAR
The STAR parameter sets the time of day for the first
defrost cycle and works in conjunction with the NDEF
parameter discussed below. This time setting is for the
initial defrost in a 24-hour period. The NDEF (number
of defrosts) determines the number of defrosts that will
occur in a 24-hour period beginning with the STAR (first
defrost) parameter. The maximum number of defrosts
allowed in a 24 hour period is 8. The defrost cycles are
spaced evenly across the 24- hour period beginning with
the STAR time. The formula for calculating defrost start
times is as follows:
Defrost interval = 24/NDEF
First defrost cycle start time = STAR
Second start time = STAR + Interval
Third start time = STAR + 2 X Interval
~
Eighth start time = STAR + 7 X Interval
4-36
P/N 0461391A
MENUS
.
TTYP
New Value
TTYP
RAIR
DAIR
TSEN
TIM
DIGI
TTYP
Value
Menu Structure — TTYP