UPS5000-S-880 kVA
User Manual (CMI)
3 Installation
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
85
Connect power cables according to port silk screens.
The length and specifications of power cables on each UPS should be the same to achieve
current equalization in bypass mode. The power cables include bypass input power cables
and UPS output power cables.
Figure 3-42
Conceptual diagram of a dual-bus parallel system
----End
3.3.2 Connecting Signal Cables
Connecting Signal Cables to a Parallel System
Connect the parallel ports on the UPSs over parallel cables to create a loop.