UPS5000-S-880 kVA
User Manual (CMI)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
128
Table 4-12
Monitoring details
Number
Area
Function
1
Running status
area
Displays the power flow and UPS running information.
2
Menu bar
Displays alarms and real-time data, sets parameters, and
provides control commands.
The
Active Alarms
page is displayed by default.
3
Information
area
Displays system monitoring information.
4.2.2.1 Parameter Settings
Figure 4-47
Parameter settings
System Settings
Item
Description
Default Value Value Range
High ambient
temperature
alarm threshold
(°C)
An alarm is generated when the
ambient temperature reaches or
exceeds the threshold specified
by this parameter.
55
40–60
Low ambient
temperature
alarm threshold
(°C)
An alarm is generated when the
ambient temperature is lower
than the threshold specified by
this parameter.
–10
–20 to 0
EPO detection
Indicates whether to enable
emergency power-off (EPO).
EPO is performed only when this
parameter is enabled and the
EPO switch is triggered.
When
EPO detection
is changed
from
Disable
to
Enable
, check
that the EPO cable is connected
correctly.
Enable
Disable, Enable
Bus capa. life
If this parameter is set to
Enable
,
Disable
Disable, Enable