UPS5000-S-880 kVA
User Manual (CMI)
2 Overview
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
24
2.3.3 Power Module
Appearance
Figure 2-10
Power module
(1) Positioning lock
(2) Run indicator
(3) Alarm indicator
(4) Fault indicator
(5) Ready switch
(6) Output port
(7) Input port
Table 2-2
Indicator description
Indicator
Color
Status
Description
Run indicator
Green
Steady on
The system is working in
mains inverter mode.
Blinking at long
intervals
The inverter is ready and
in standby state (blinking
at 0.5 Hz, on for 1s and
off for 1s).
The inverter is not started