UPS5000-S-880 kVA
User Manual (CMI)
5 Operations
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
156
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair.
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
Step 2
(Optional) On the MDU, choose
System Info
>
Settings
>
DST Settings
and set the DST
mode as required.
Step 3
After you set parameters on the
Settings Wizard
screen, the MDU displays the
Bypass mode
and
No battery
alarms, which do not need to be handled. If there is any other alarm, you need
to rectify the fault.
After you set parameters on the
Settings Wizard
screen, choose
System Info
>
Settings
>
System
Settings
. Check that
Requisite modules
and
Redundant modules
match the actual values.
If dry contact signals are connected to the system, choose
System Info
>
Settings
>
Dry Contact
Set
and check that the connected dry contacts have been enabled and that the disconnected dry
contacts have been disabled.
Step 4
View the system running diagram on the MDU to check that the UPS is working in bypass
mode.
----End
The
Service Expert
app can be downloaded from Google Play and can run on
Android. User interfaces displayed in this document correspond to the app version
V100R001C00B055 and are for reference only.
For offline startup, enter the barcode and the verification code on the mobile phone app.
The app automatically generates a startup password for the UPS. Then enter the password
on the MDU screen to start the UPS.
For online startup, activate the startup password on the mobile phone app to start the UPS.
If the initial startup verification passes, startup verification is not required afterwards.
After factory settings are restored, re-verification for startup is required.
Online Startup
Step 1
Insert a WiFi module into the USB port on the MDU.
Step 2
Enable the mobile phone WLAN, search for the UPS WiFi signal, and connect to the WiFi
signal. The default value of
SSID
is
UPS_WIFI
.
The initial WiFi password is
Changeme
by default. You can change the password by choosing
System
Info
>
Settings
>
Comm Settings
>
WiFi Settings
on the MDU.
Step 3
Open the
Service Expert
app on the mobile phone.
Step 4
On the home screen of the app, tap
Startup
to access the
Set Startup