131
Item
Description
Default Value Value Range
the system. This parameter
specifies the number of transfers
between bypass mode and
normal mode within 1 hour,
which ensures system security.
Current equal.
detection
Monitors the current differences
between racks or modules. If this
parameter is set to
Enable
, the
Mod. Cur. Eql. Data
can be
viewed on the running
information screen.
Disable
Disable, Enable
Inverter async.
alarm
Specifies whether an
Inverter
asynchronous
alarm can be
displayed on the LCD when the
inverter cannot track the bypass
frequency change. Normal power
supply is not affected no matter
whether this parameter is set to
Enable
or
Disable
.
Disable
Disable, Enable
Bus
overvoltage
recovery
Specifies whether to
automatically clear the alarm and
restart the power module when
the rectifier or inverter shuts
down due to a bus overvoltage
alarm. If
Bus overvoltage
recovery
is set to
Enable
, the
bus overvoltage alarm is
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers (less than 420
V) within
Bus overvolt.
recovery time
. When
Bus
overvoltage recovery
is set to
Disable
, the bus overvoltage
alarm cannot be automatically
cleared, and the rectifier and
inverter cannot automatically
start.
Enable
Disable, Enable
Bus overvolt.
recovery time
If
Bus overvoltage recovery
is
set to
Enable
, the bus
overvoltage alarm is
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers (less than 420
V) within
Bus overvolt.
recovery time
.
5s
5s, 1 min, 5 min,
10 min
Capacitor
failure
If
Capacitor failure detection
is
set to
Enable
, the power module
Disable
Disable, Enable