Alarm ID
(Alarm ID-
Alarm
Cause ID)
Alarm Name Severity
Cause
Solution
input breaker
open
circuit breaker on the
PDF is OFF.
There are no suggested measures.
0338
PDF output
breaker open
Critical
The output circuit
breaker on the PDF is
OFF.
1.
Check that all UPS output circuit
breakers are ON.
2.
On the LCD, check that PDF
output breaker open alarm has
disappeared. If the alarm persists,
tap the
Clear Fault
button to
clear the alarm.
0341
PDF Maint.
breaker closed
Minor
The maintenance
circuit breaker on the
PDF is ON.
The running status is displayed.
There are no suggested measures.
0342
Mains input
breaker open
Critical
The mains input circuit
breaker is OFF.
The running status is displayed.
There are no suggested measures.
0343
Bypass input
breaker open
Critical
The bypass input
circuit breaker is OFF.
The running status is displayed.
There are no suggested measures.
0335
Generator
connected
Warning
The generator is
connected.
The running status is displayed.
There are no suggested measures.
0594-1
Insufficient
redundant
racks
Minor
The load is
excessive.
The configured
number of
redundant racks is
incorrect.
1.
Reduce the load.
2.
Decrease the configured number
of redundant racks.
0095-1
Insuffi.
redundancy
Minor
The load is
excessive.
The configured
number of
redundant modules
is incorrect.
1.
Reduce the load.
2.
Decrease the configured number
of redundant modules.
0096-1
ECO volt.
abnormal
Minor
The ECO bypass
voltage or
frequency is out of
the preset range.
The ECO bypass
voltage or
frequency range is
incorrectly set.
The bypass input
sequence is reverse
or the neutral wire
is disconnected.
1.
Check the bypass input voltage
and frequency.
2.
Check that the rated voltage,
rated frequency, ECO bypass
voltage range, and frequency
range are correctly set.
3.
Check that the ECO bypass
cables and circuit breakers are
correctly connected.