UPS5000-S-880 kVA
User Manual (CMI)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
130
Item
Description
Default Value Value Range
time site
waveform
one waveform can be stored
manually.
BCB trips in
case of EOD
If this parameter is set to
Enable
,
the BCB will trip in case of
EOD.
Enable
Disable, Enable
Input Settings
Item
Description
Default Value Value Range
Input
adaptability
The value of
Input adaptability
can be
Strong
or
Weak
. Strong
input adaptability applies to the
D.G. or input sources whose
input current has high frequency
oscillation. In this mode, the total
distortion of the input current
waveform (THDi) is poor, but
the system is stable. Weak input
adaptability is suitable for mains
and AC input sources.
Strong
Strong, Weak
Output Settings
Item
Description
Default Value Value Range
Zero display
with no load
output
If this parameter is set to
Enable
,
the output current is displayed as
0 when no load is output. The
output load rate is displayed as
3%. When this parameter is set to
Disabled
, the output current and
output load rate are not adjusted
to zero.
Enable
Disable, Enable
Calib. output
current if no
load
If this parameter is set to
Enable
,
the current at no load will be
calibrated once automatically.
This function can be used only
when the UPS carries no load.
Disable
Disable, Enable
Output
interruption
transfer time
(ms)
Set this parameter based on the
output interruption time
acceptable to loads.
0
0 ms, 40 ms, 60
ms, 80 ms, 100
ms, 120 ms
Max. BPM
transfer times
Cross currents occur during the
transfer between bypass mode
and normal mode, which impacts
5
1–10