UPS5000-S-880 kVA
User Manual (CMI)
5 Operations
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
163
Figure 5-10
BCB connection setting
----End
5.2 Shutting Down and Powering Off the UPS
Context
After you shut down the inverter, the UPS transfers to bypass mode if the bypass is normal;
the UPS supplies no power if the bypass is abnormal. Before shutting down the UPS, ensure
that all loads have been shut down.
Procedure
Step 1
Shut down the inverter.
On the LCD
On the main menu, choose
Common Functions
and tap
Inv. ON
.
Alternatively, tap
System Info
>
Maintenance
to shut down the inverter on the
Maintenance
screen.
On the WebUI
Choose
Monitoring
>
Control
, and click
Inv. OFF
. In the displayed dialog box, click
OK
to shut down the inverter.
After the inverter shuts down, the UPS works in bypass mode if the bypass is normal, as
shown in
; the UPS supplies no power and the loads power off if the bypass