UPS5000-S-880 kVA
User Manual (CMI)
3 Installation
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
48
Port Description Connection Mode Bolt
Specifications
Bolt Hole
Diameter
Bolt
Length
Torque
terminal
Battery input
Crimped DT
terminal
M16
18 mm
50 mm
120 N·m
Output
Crimped DT
terminal
M16
18 mm
50 mm
120 N·m
PE connectors
Crimped DT
terminal
M12
N/A
35 mm
47 N·m
Table 3-4
Recommended upstream input and downstream output circuit breakers
UPS Capacity
Component
Specifications
880 kVA
Mains input circuit breaker
2000 A/3P
Bypass input circuit breaker 1600 A/3P
Downstream output circuit
breaker
1600 A/3P
If multiple loads are connected, use recommended specifications for branch circuit breakers.
The circuit breaker selection rule is to protect loads and cables, and the cascading rule is to achieve
specific protection.
3.1.4 Unpacking
Context
Only trained personnel are allowed to move the UPS. Use a pallet truck to transport the
UPS box secured to a wooden support to the installation position.
To prevent the UPS from falling over, secure it to an electric pallet truck using ropes
before moving it.
To prevent shocks or falls, move the UPS gently. After placing the UPS in the installation
position, unpack it with care to prevent scratches. Keep the UPS steady during unpacking.
If the UPS installation environment is in poor condition and the UPS will be stored for a
long time after it is unpacked, wrap the UPS with the original plastic coat to prevent dust.
Procedure
Step 1
Use a pallet truck to transport the UPS to the installation position.