3.4 Electrical connection
Unit type
MG-6/30
MG-6/60
MG-9/60
Supply voltage
V AC
400 3N
400 3N
400 3N
Permitted voltage tolerance
%
+10 / -15
+10 / -15
+10 / -15
Frequency
Hz
50
50
50
Power consumption
at rated heating capacity
W
697
1127
1127
at minimal capacity
W
517
657
657
in standby mode
W
7
7
7
Current consumption max.
A
1.7
2.7
2.7
Protection rating
–
IP 20
IP 20
IP 20
Table E5: TopVent
®
MG electrical connection
3.5 Gas connection
Unit type
MG-6/30
MG-6/60
MG-9/60
Gas appliance type
1)
B
23
, C
13
, C
33
Gas connection
Rp ½ " (internal) R ¾" (external) R ¾" (external)
Combustion air connection
DN 80
DN 100
DN 100
Flue gas connection
DN 80
DN 100
DN 100
Max. length of flue gas duct
2)
9 m
9 m
9 m
1) According to method of flue gas evacuation and combustion air supply
2) Equivalent length of formed parts:
– 90° elbow ..... 2 m
– 45° elbow .... 1 m
– 90° T-piece ... 2 m
Table E6: TopVent
®
MG gas circuit connections
3.6 Sound levels
Unit type
MG-6/30
MG-6/60
MG-9/60
Fan speed
1
2
1
2
1
2
Sound pressure level (at a distance of 5 m)
1)
dB(A)
46
53
48
54
49
55
Total sound power level
dB(A)
68
75
70
76
71
77
Octave sound power level
63 Hz
dB
71
79
76
81
77
82
125 Hz
dB
68
75
72
80
73
81
250 Hz
dB
71
77
72
78
73
79
500 Hz
dB
65
73
69
73
70
74
1000 Hz
dB
62
70
65
71
66
72
2000 Hz
dB
58
67
60
67
61
68
4000 Hz
dB
51
61
54
61
55
62
8000 Hz
dB
47
55
49
56
50
57
1) With a hemispherical radiation pattern in a low-reflection room
Table E7: TopVent
®
MG sound power levels
52
TopVent
®
MG
Technical data
Содержание DGV-6/30
Страница 2: ......
Страница 4: ...2...
Страница 5: ...Safety A 1 Symbols 4 2 Operational safety 4 3 Information for a user manual 4 3 Safety Content...
Страница 20: ...18...
Страница 34: ...32...
Страница 76: ...74...
Страница 77: ...Operation I 1 Operation 76 2 Maintenance and repair 77 3 Dismantling 78 4 Disposal 78 75 Operation Content...
Страница 81: ......