5 Design example
Notice
Use the 'HK-Select' program to design Hoval Indoor Climate Systems.
You can download it free of charge on the Internet.
Design data
Example
■
Geometry of the room
■
Internal heat gains
■
Fabric heat losses
■
Fresh air temperature
■
oom temperature
■
Extract air temperature
■
Comfort requirements (acoustic)
■
People in the room
■
Improvement of air quality, fresh air supply for the people in the room
(fresh air flow rate per person = 30 m³/h)
Geometry ..................................50 × 60 × 12 m
Internal heat gains ....................28 kW
Fabric heat loss .........................350 kW
Fresh air temperature................– 15 °C
Room temperature ....................18 °C
Extract air temperature..............20 °C
Comfort requirements ...............Standard
20 people
Comfort requirements
Define the fan speed in accordance with the acoustic requirements:
■
Low noise level
→
Fan speed 1
■
Normal noise level
→
Fan speed 2
Standard
→
Fan speed 2
Fresh air supply
■
Required fresh air flow rate in total:
■
Fresh air ratio of supply air units: max. 10 % of the nominal air flow rate
The fresh air ratio can be adjusted from 0…100 %. Where EU Regulation 1253/2014
applies, it must be restricted to max. 10 % in the design conditions.
■
Calculate the required number of supply air units from the nominal air flow rate.
20 × 30 = 600 m³/h
MG-6/30: max. 420 m³/h fresh air
MG-6/60: max. 590 m³/h fresh air
MG-9/60: max. 700 m³/h fresh air
→
1 TopVent
®
MG-9/60 unit
Mounting height
■
Calculate the actual mounting height (= distance between the floor and the bottom edge of
the TopVent
®
unit).
H = Hall height – distance from ceiling – unit height
■
Compare the actual mounting height with the minimum and maximum mounting height (see
Supply air units:
Size 6
→
OK
Size 9
→
OK
Recirculation units:
Size 6
→
OK
Size 9
→
OK
Required performance for covering fabric heat losses
■
Required heat output for coverage of fabric heat losses in total
Q
H_req
= Fabric heat losses – internal heat loads
350 – 28 = 322 kW
E
55
TopVent
®
MG
Design example
Dimensions and weights
Содержание DGV-6/30
Страница 2: ......
Страница 4: ...2...
Страница 5: ...Safety A 1 Symbols 4 2 Operational safety 4 3 Information for a user manual 4 3 Safety Content...
Страница 20: ...18...
Страница 34: ...32...
Страница 76: ...74...
Страница 77: ...Operation I 1 Operation 76 2 Maintenance and repair 77 3 Dismantling 78 4 Disposal 78 75 Operation Content...
Страница 81: ......