3 Technical data
3.1 Type codes
GV - 3 / 30 / ...
Unit type
TopVent
®
GV
Unit size
3 or 5
Output in kW
30 or 50
Options
Table D2: TopVent
®
GV unit type reference
3.2 Application limits
Ambient temperature
min.
°C
- 15
max.
°C
35
Supply air temperature
max.
°C
60
The units cannot be used in:
■
Damp locations
■
Places with a corrosive or aggressive environment
■
Spaces with a large amount of dust
■
Areas where there is danger of explosion
Table D3: TopVent
®
GV application limits
3.3 Air flow rate, gas consumption
Unit type
GV-3/30
GV-5/50
Nominal air flow rate
1)
m³/h
2600
5150
Floor area reached
2)
m²
70
115
Nominal heat input
max.
kW
32.0
54.9
Nominal heat output
max.
kW
29.2
49.9
Combustion efficiency
3)
%
min. 91
min. 91
Emissions of nitrogen oxides (GCV)
mg/kWh
35.0
41.0
Emission efficiency
%
90.6
91.2
Seasonal space heating energy efficiency
%
72.8
74.1
Gas consumption
Natural gas: G20, G27 (H, E, Lw)
m³/h
3.4
5.8
Natural gas: G25, G25.3 (L, LL, K)
m³/h
3.8
6.6
1) at an air temperature of 20 °C
2) with vertical air flow
3) in accordance with EN 1020
Table D4: TopVent
®
GV technical data
36
TopVent
®
GV
Technical data
Содержание DGV-6/30
Страница 2: ......
Страница 4: ...2...
Страница 5: ...Safety A 1 Symbols 4 2 Operational safety 4 3 Information for a user manual 4 3 Safety Content...
Страница 20: ...18...
Страница 34: ...32...
Страница 76: ...74...
Страница 77: ...Operation I 1 Operation 76 2 Maintenance and repair 77 3 Dismantling 78 4 Disposal 78 75 Operation Content...
Страница 81: ......