5 Design example
Notice
Use the 'HK-Select' program to design Hoval Indoor Climate Systems. You
can download it free of charge on the Internet.
Notice
As a general principle, Hoval recommends vertical air flow, that is, that the
units be ceiling-mounted. Use horizontal air flow if ceiling-mounting is not
possible due to the particular conditions (added constructions, mounting
height).
5.1 Vertical air flow
Design data
Example
■
Geometry of the room
■
Fabric heat losses
■
Room temperature
■
Extract air temperature
(Because of the low height, room temperature = extract air temperature is used in this example.)
■
Distance from ceiling
Geometry ..................................15 × 20 × 4 m
Fabric heat losses .....................38 kW
Room temperature ....................20 °C
Extract air temperature..............20 °C
Distance from ceiling .................0.6 m
Mounting height
■
Calculate the actual mounting height (= distance between the floor and the bottom edge of
the units).
H = Hall height – distance from ceiling – unit height
■
Compare the actual mounting height with the minimum and maximum mounting height
GV-3/30
→
OK
GV-5/50
→
OK
Minimum number of units
■
Determine the minimum number of units for each unit type. Take into account the following criteria:
–
Floor area covered
–
Heat output
–
Unit clearances
Type
Required number
Minimum number
of units
Floor area covered
Heat output
Unit clearances
GV-3/30
5
2
6
6
GV-5/50
3
1
4
4
■
Choose the final solution from the remaining possibilities, depending on the geometry of the hall and the costs.
40
TopVent
®
GV
Design example
Содержание DGV-6/30
Страница 2: ......
Страница 4: ...2...
Страница 5: ...Safety A 1 Symbols 4 2 Operational safety 4 3 Information for a user manual 4 3 Safety Content...
Страница 20: ...18...
Страница 34: ...32...
Страница 76: ...74...
Страница 77: ...Operation I 1 Operation 76 2 Maintenance and repair 77 3 Dismantling 78 4 Disposal 78 75 Operation Content...
Страница 81: ......