3.7 Heat output
Room air temperature
16 °C
20 °C
Unit type
Fan speed
Q
t
S
H
max
Q
t
S
H
max
kW
°C
m
kW
°C
m
NGV-6/30
1
29.2
38.7
8.8
29.2
42.7
8.9
2
29.2
32.7
13.8
29.2
36.7
13.9
NGV-6/60
1
60.5
51.9
8.8
60.5
55.9
8.9
2
60.5
43.0
13.3
60.5
47.0
13.4
NGV-9/60
1
60.5
44.4
9.0
60.5
48.4
9.1
2
60.5
38.4
12.7
60.5
42.4
12.8
Legend:
Q
= Nominal heat output
t
S
= Maximum supply air temperature
H
max
= Maximum mounting height
Reference:
■
At room air temperature 16 °C: extract air temperature 18 °C
■
At room air temperature 20 °C: extract air temperature 22 °C
Table C8: TopVent
®
NGV heat output, supply air temperatures and mounting height
3.8 Minimum and maximum distances
X/2
X
Z
H
Unit type
NGV-6/30
NGV-6/60
NGV-9/60
Fan speed
1
2
1
2
1
2
Unit clearance X
min.
m
10
11
11
13
12
14
max.
m
19
23
21
26
25
30
Mounting height H
min.
m
4.0
4.0
4.0
4.0
5.0
5.0
Distance from ceiling Z
min.
m
0.3
0.3
0.3
0.3
0.4
0.4
Table C9: TopVent
®
NGV minimum and maximum distances
■
1
Allow a free space of 1.5 m for service
and maintenance.
C
25
TopVent
®
NGV
Technical data
Technical data
Содержание DGV-6/30
Страница 2: ......
Страница 4: ...2...
Страница 5: ...Safety A 1 Symbols 4 2 Operational safety 4 3 Information for a user manual 4 3 Safety Content...
Страница 20: ...18...
Страница 34: ...32...
Страница 76: ...74...
Страница 77: ...Operation I 1 Operation 76 2 Maintenance and repair 77 3 Dismantling 78 4 Disposal 78 75 Operation Content...
Страница 81: ......