8.4 Electrical installation
Caution
Danger of electric shocks. The electrical installation is
to be carried out only by a qualified electrician!
■
Observe all relevant regulations (e.g. EN 60204-1).
■
Check whether the local operating voltage, frequency and
fuse protection match the data on the type plate. If there
are any discrepancies, the unit must not be connected!
■
Cable cross-sections must be selected according to tech
-
nical regulations, e. g. VDE 0100.
■
Electrical installation to be carried out according to wiring
diagram.
■
Do not forget the master switch for the complete
installation.
A TempTronic can control up to 8 TopVent
®
units
simultaneously:
■
Connect TempTronic and the units to each other via a
system bus.
■
With micro switch J14 on the burner control, assign to
each unit a number of its own.
■
Set switch S1 on the pilot unit burner control in position '1',
and in the other units in position '0'.