Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Chart
1.Operation Flow Chart
FS
check
1 to 3-min. harvest timer
in
control (S4 dip switch
1 & 2)
Legend:
BC
–bin control
CB
–control board
Comp
–compressor
FM
–fan motor
FS
–float switch
HGV
–hot gas valve
HPT
–harvest pump time
LLV
–liquid line valve
PM
–pump motor
WV
–inlet water valve
Components Energized when the Control Switch is in the "W
ASH" Position
The "W
ASH" position on the control switch is used when cleaning and sanitizing the unit. When in the "W
ASH" position, power is supplied to
the pump motor
. With the cleaning valve closed, the cleaner and sanitizer flow over the outside of the evaporator plate assembly
. With the
cleaning valve open, the cleaner and sanitizer flow over both the outside and the inside of the evaporator plate assembly
.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not restart when the control
switch is placed in the "ICE" position.
Operation Flow Chart
1. 1-Minute
Fill Cycle
Cycle
Steps
2. Harvest Cycle
• WV
time: 6 min. or the length of harvest minus HPT
setting (S4 dip switch 6), whichever is shorter
.
• Max. harvest time: 20 min.
Thermistor in control
3. Freeze Cycle
• Min. freeze time: 5 min. • Max. freeze time: freeze timer setting (S4
dip switch 9 & 10).
FS
in control
4. Pump-Out Cycle
• Factory set for every
10th cycle
(S4 dip switch 5)
• Pump motor stops for
2
sec., then reverses for
10/20 sec.
(S4 dip switch 3 & 4)
WV
energized
FS
open
Comp
energized
FM
energized
HGV
energized
WV
energized
Thermistor temperature reaches
9°C(3.9
kΩ or less). Harvest timer
starts.
FS
open
Comp
energized
FM
energized
PM
energized
LLV
energized
HGV
de-energized
FS
closed
Comp
energized
FM
energized
HGV
energized
PM
de-energizes for 2 sec.,
then reverses for 10/20 sec.
LLV
de-energized
FS
check
Startup
If
FS
is open, Comp stops and cycle
returns to 1-Min. fill.
5-min. minimum freeze timer in control
FS
closed
FS
opens or freeze
timer terminates
50 sec.
PM
energized
WV
de-energized
Harvest Pump Time
Anti-Slush
Thermistor temperature reaches 2.2°C
(5.8 kΩ).
PM
de-energized for
10 sec.