34
11. Minimum Harvest Time (S5 dip switch 4)
NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside the factory
default setting may result in damage to the appliance.
S5 Dip Switch Setting
Minimum
Harvest Timer
No. 4
OFF
120 sec.
ON
70 sec.
12. Anti-Slush (S5 dip switch 5)
NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside the factory
default setting may result in damage to the appliance.
This dip switch setting provides anti-slush control during the freeze cycle. When the
evaporator temperature reaches 2.2°C the control board reads a 5.8kΩ signal from the
thermistor and de-energizes the water pump for 10 sec. to melt ice slush and prevent ice
slush from blocking the water supply tubing, causing irregular freeze patterns.
S5 Dip Switch Setting
Anti-Slush
No. 5
OFF
Disabled
ON
Enabled