68-0139
8
W180 ZONE CONTROL SYSTEM
Specifications
NOTE: The specifications given in this publication do not
include normal manufacturing tolerances. Therefore, an
individual unit may not exactly match the listed specifi-
cations. Also, the products are tested and calibrated
under closely controlled conditions and some minor
differences in performance can be expected if those
conditions are changed.
W180A CONTROLLER
MODEL: W180A1001.
POWER INPUT: 24 Vac/40 VA (transformer not included,
but is required).
POWER CONSUMPTION: 40 VA max.
INPUTS: 16 analog/digital inputs configurable as switch,
temperature, or general purpose type sensors.
OUTPUTS: 24 relays configured in 12 relay pairs. Each
relay in a pair can be configured for individual devices
that are powered from a common source.
PORTS: RS-232 for PC communication.
NUMBER OF W180 SYSTEMS THAT CAN BE CON-
NECTED TO A HONEYWELL TotalHome
®
SYSTEM:
One; using HBus communications. Additional W180
Systems can be connected to TotalHome
®
only through
contact closures to the W180 input configured as a Pro-
file Trigger input.
NUMBER OF ZONES:
Maximum of 16 for heating only or cooling only sys-
tems, depending on the application and equipment.
Maximum of 10 for heating and cooling forced air sys-
tems, depending on the application and equipment.
1 [44]
2
[51]
17
[432]
15
[400]
3
4
1
1
2
[38]
2 1
2
[64]
7
1
2
[191]
2
[51]
3 [76]
7
1
2
[191]
15
1
2
[394]
19 [483]
20 [508]
5
3
8
[137]
2
[51]
5 [127]
13 [330]
UPSET KNOCKOUT, 9 PLCS
1 3/8 SMALL DIA.
1 3/4 LARGE DIA.
M8158
3
4
Fig. 2—W180A Controller Enclosure dimensions in in. [mm].
Содержание W180
Страница 50: ...68 0139 50 W180 ZONE CONTROL SYSTEM ...