37
68-0139
W180 ZONE CONTROL SYSTEM
2. Wire the sensor as shown in the job drawings and
Figs. 40 through 42.
3. Mount the space sensor circuit board on the mount-
ing plate (Fig. 43).
4. Mount the cover on the mounting plate (Fig. 44).
Fig. 40—T7660A Space Temperature Sensor
terminal connections.
Fig. 41—Typical T7660A Space Temperature
Sensor wiring.
LED
T
A
D
W1
PB
LED LIGHT
TEMPERATURE
SENSOR
ANALOG;
COMMON
DIGITAL;
COMMON
PUSHBUTTON
JUMPER W1
M8162
–1
+1
–2
+2
–3
+3
–4
+4
–5
+5
–6
+6
–7
+7
–8
+8
SENSOR/INPUT
CONNECTIONS
M8174
18-22 AWG
TWISTED PAIR
HONEYWELL T7660A SENSOR
MAXIMUM DISTANCE FROM CONTROLLER
IS 300 FT. [91 M] USING 18 AWG
THERMOSTAT WIRE.
T
A
SENSOR GND
CABLE SHIELD
(IF REQUIRED)
T7660A SENSOR
Fig. 42—Typical T7660B Space Temperature Sensor wiring.
–1
+1
–2
+2
–3
+3
–4
+4
–5
+5
–6
+6
–7
+7
–8
+8
SENSOR/INPUT
CONNECTIONS
M8175
22 AWG
SENSOR GND
SENSOR PWR
T7660B SENSOR
RLY 1
1/2 com
RLY 2
spare A
RLY 3
3/4 com
RLY 4
spare B
spare C
RLY 5
5/6 com
RLY 6
spare D
RLY 7
7/8 com
RLY 8
RELAY
CONNECTIONS
20 VDC
5 VDC
RTD SENSOR WIRES
R2
R1
220 ,
1/8 WATT
2.2K,
1/4 WATT
T
A
D
LED
PB
Содержание W180
Страница 50: ...68 0139 50 W180 ZONE CONTROL SYSTEM ...