![Honeywell W180 Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/honeywell/w180/w180_user-manual_149171030.webp)
68-0139
30
W180 ZONE CONTROL SYSTEM
Fig. 27—Wiring three S321A Touchpads to the W180A Controller.
M8170
SHIELD GROUNDED
AT W180A CONTROLLER
CHASSIS GROUND
TOUCHPADS
YELLOW
YELLOW
GREEN
GREEN
RED
BLACK
+
–
+
–
+
–
+
–
DATA
END
12 VDC
12 VDC
external
int.
YELLOW
GREEN
RED
BLACK
YELLOW
GREEN
RED
BLACK
YELLOW
GREEN
RED
BLACK
POWER CONNECTIONS:
18 AWG, SOLID OR STRANDED
SIGNAL CONNECTIONS:
TWISTED PARIS, SHIELDED, 24 AWG STRANDED
HBUS WIRING NOTES:
1. USE 6-CONNECTOR, 3 TWISTED PAIR SHIELDED CABLE, 18 GAUGE.
2. IF POWER IS RUN IN SEPARATE CABLE, DATA CABLE CAN BE 24 GAUGE AS SHOWN, DISTANCE LESS THAN 400 FT. [120 M].
3. POWER CABLING = 2.8V DROP AT MAXIMUM LOAD.
4. GROUND DATA CABLE SHIELD TO ENCLOSURE CHASSIS.
5. DO NOT EXTEND YELLOW OR GREEN WIRES COMING FROM TOUCHPADS WITH A SINGLE WIRE.
ONLY CONNECT DATA LINES DIRECTLY AS SHOWN ABOVE.
JUMPER
BLOCK
Fig. 28. Auxiliary power wiring for wiring more than three S321A Touchpads to the W180A Controller.
+
+
–
–
+
–
+
–
+
–
DATA
END
12 VDC
12 VDC
EXTERNAL
int.
PLACE JUMPER
TO CONNECT
THE TWO LEFT
HEADER PINS
(SIDE OPPOSITE
INT)
LEAD
LEAD
12 Vdc POWER SUPPLY
(USE POWER SUPPLY
RATED AT 250 mA PER
TOUCHPAD)
1 TOUCHPAD = 250mA
2 TOUCHPADS = 500mA
3 TOUCHPADS = 750mA
4 TOUCHPADS = 1 A
5 TOUCHPADS = 1.25 A
SAMPLE POWER SUPPLIES:
-ALTRONIX SMP3 POWER SUPPLY (2.5 A)
-AlarmSaf ASPS1 (1.0 A)
WIRING NOTES:
1. DISCONNECT POWER SUPPLY BEFORE BEGINNING INSTALLATION.
2. AN EXTERNAL POWER SUPPLY IS REQUIRED WHEN CONNECTING
MORE THAN THREE S321A TOUCHPADS TO ONE W180A CONTROLLER.
3. USE ANY 12 Vdc REGULATED OR UNREGULATED PLUG-IN OR
STANDARD SECURITY SYSTEM AUXILIARY POWER SUPPLY.