W180 ZONE CONTROL SYSTEM
TABLE 9—WIRING (Continued).
Device
Mounting Location
Notes
198212CA Outdoor
Temperature Sensor
Away from radiation from sun, preferably
on north wall.
7.
Accessory Cables (ft [m]):
a. 4074CAV: shielded cable, 50 [15].
C7130A Wall
Mount Room
Temperature Sensor
On inside wall about 5 ft [1.5m] above
floor, away from hot or cold areas, water
pipes, air ducts, discharge air, and radia-
tion from lights, appliances, and the sun.
b. 4074CAW: shielded cable, 100 [30.4].
c. 4074CAY: shielded cable, 200 [61].
T7660A Space
Temperature Sensor
T7660B Space
Temperature Sensor
with Occupied
Override
C7600C Solid State
Humidity Sensor
Where it is exposed to freely circulating
air (500 ft/min minimum air flow), but
protected from rain and direct sunlight.
8.
Connect the 20 Vdc input wire from the
W180A to the + terminal. Connect the
W180A analog input wire to the sensor–
terminal.
AOBD Honeywell/
Trol-A-Temp
®
Rectangular
Dampers
Where required.
9.
Requires transformer separate from the
W180A Controller transformer. Five damper
actuators (max) per 40 VA transformer.
10. Use a modified 3-wire daisy chain wiring
technique to simplify wiring or use five wires
and wire as home runs.
D635B-G Zone
Dampers
Where required.
11. Requires transformer separate from the
W180A Controller transformer. Eighteen
damper actuators (max) per 40 VA
transformer.
12. Use the daisy chain wiring technique to
simplify wiring and eliminate multiple wires
at the W180A Controller.
V8043A,B,E,F,J
V8044A,B,E
Motorized Valves
Where required.
13. Requires transformer separate from the
W180A Controller transformer. Five V8043
Zone Valves (max) per 40 VA transformer.
14. On all hydronic systems, the W180A must
have direct and independent control of all
valves and pumps. Therefore, valve end
switches must not control circulation pumps.