68-0139
18
W180 ZONE CONTROL SYSTEM
HVAC CONFIGURATION TABLE (Continued).
Function
Definition
Minimum
Maximum
Default
Anticipation
—Heat
For heating equipment. A value greater than 1
increases the equipment cycle rate; a value less
than 1 decreases the equipment cycle rate.
Recommended values:
—Electric: 1.5.
—Forced Air: 1.2.
—Heat Pump: 1.0.
—Hydronic/Radiant: 0.8.
0.0
1.5
1.0
Anticipation
—Cool
For cooling equipment. A value greater than 1
increases the equipment cycle rate; a value less
than 1 decreases the equipment cycle rate.
Recommended values:
—Cooling Compressor: 1.0.
0.0
1.5
1.0
Overrun
Time—Heat
The length of time in minutes the fan defined
for this stage is active following a call for
heating.
0
30
2
Overrun
Time—Cool
The length of time in minutes the fan defined
for this stage is active following a call for
cooling.
0
30
2
Minimum Off
Time—Heat
The length of time in minutes that must expire
following a call for heating before the stage
equipment may be activated again.
3
30
3
Minimum Off
Time—Cool
The length of time in minutes that must expire
following a call for cooling before the stage
equipment may be activated again.
3
30
3
Lockout
Temperature
—Heat
When the outdoor temperature is above this
temperature, the stage is locked out.
10
°
F
99
°
F
90
°
F
Lockout
Temperature
—Cool
When the outdoor temperature is below this
temperature, the stage is locked out.
10
°
F
99
°
F
50
°
F
Outside Temp
for Alt. Eq.—
Heat
When the actual outdoor temperature is below
this value, any heating equipment set up during
configuration as Alt. Eq.—Heat will be
activated in place of the equipment defined as
Normal—Heat.
10
°
F
99
°
F
40
°
F
Outside Temp
for Alt. Eq.—
Cool
When the actual outdoor temperature is above
this value, any cooling equipment set up during
configuration as Alt. Eq.—Cool will be
activated in place of the equipment defined as
Normal—Cool.
10
°
F
99
°
F
90
°
F
Stage
Differential—
Heat
The number of degrees below setpoint the
average zone demand must exceed before this
stage is activated.
1st Stage: 0
°
F
2nd Stage: 1st Stage
+ 1
°
F
3rd Stage: 2nd Stage
+ 1
°
F
1st Stage: 20
°
F
2nd Stage: 20
°
F
3rd Stage: 20
°
F
1st Stage: 0
°
F
2nd Stage: 4
°
F
3rd Stage: 6
°
F
Stage
Differential—
Cool
The number of degrees above setpoint the
average zone demand must exceed before this
stage is activated.
1st Stage: 0
°
F
2nd Stage: 1st Stage
+ 1
°
F (1
°
F)
3rd Stage: 2nd Stage
+ 1
°
F (2
°
F)
1st Stage: 20
°
F
2nd Stage: 20
°
F
3rd Stage: 20
°
F
1st Stage: 0
°
F
2nd Stage: 4
°
F
3rd Stage: 6
°
F
Stage
Attributes—
Emergency
Heat
Use this equipment during manual system
override to Emergency Heat mode in place of
the first stage heat pump equipment in heating.