68-0139
16
W180 ZONE CONTROL SYSTEM
PC REQUIREMENTS
1. IBM
®
PC/AT™ or compatible 286, 386, or 486
personal computer. The 386 or 486 personal computer are
recommended.
2. At least 4 MB of RAM.
3. MS-DOS version 5.0 or later.
4. Microsoft
®
Windows™ version 3.1 or later.
5. A 20 MB (minimum) hard disk drive. A 40 MB or
larger hard disk drive is recommended.
6. A 3-1/2 or 5-1/4 in., high-density disk drive.
7. A serial or bus mouse.
8. Serial port for RS-232 connection to W180A
Controller.
9. Serial port for serial mouse, if used.
10. RS-232 interconnect cable from the W180A Con-
troller to the PC (Fig. 13).
Fig. 13—RS-232 Cable pin-out.
W180 PROGRAMMING CABLE
W180 TO 9 PIN SERIAL PORT CABLE CONNECTIONS
(HONEYWELL PART NO. 204162)
W180
(FEMALE)
PC SERIAL PORT
(FEMALE)
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
•
•
•
24
25
RXD
TXD
GND
RXD
TXD
GND
W180
(FEMALE)
PC SERIAL PORT
(FEMALE)
RXD
TXD
GND
RXD
TXD
GND
W180 TO 25 PIN SERIAL PORT CABLE CONNECTIONS
(HONEYWELL PART NO. 204119 ; WITH NULL MODEM 204169)
M8160
Application
GENERAL
The following must be accomplished to properly plan a
job and order the equipment:
— Determine the W180 System requirements:
• Required equipment, zones served, and number
of stages.
• Required auxiliary equipment.
• Zoning requirements and the number and type
of sensors, dampers, and valves.
• Power requirements.
• Inputs (including special inputs) and outputs.
• Number of S321A Touchpads.
• Equipment mounting locations.
• Wiring.
— Determine the Temperature Profiles.
CAUTION
To prevent damage to the W180A Controller, do
not connect either side of the 24 Vac transformer
secondary that is used to power the W180A Con-
troller to earth ground.