3
68-0139
W180 ZONE CONTROL SYSTEM
W180 Zone Control System Overview
This manual presents application information and in-
stallation, checkout, and troubleshooting procedures for the
W180 Zone Control System (W180 System) (Fig. 1). The
W180 System is used to optimize comfort and energy
savings in a variety of residential and light commercial
applications.
The W180 System:
— Can operate with the Honeywell TotalHome
®
Sys-
tem (versions 1.14 and greater), providing remote
access and control for the homeowner. W180 Pro-
files and settings can change automatically with
TotalHome
®
Modes.
— Can control different types of HVAC equipment (for
example, radiant hydronic heating and air condition-
ing) as well as multiple sets of equipment (for ex-
ample, four air conditioning units and four furnaces).
— Allows central control with the easy-to-use S321A
Touchpad.
— Allows multiple S321A Touchpads to be located
throughout the house or building for convenient
operation.
— Supports a maximum of three Touchpads with the dc
power supply provided by the W180A Controller.
— Allows unique and personalized names to be defined
for each zone.
— Allows user to individually adjust settings in each zone.
— Has user-definable, system-wide Temperature Pro-
files for quick, easy control and adjustments.
— Permits separate temperature setpoints (for each zone)
for any Temperature Profile.
— Allows PC interface for configuration and monitoring.
— Supports a wide variety of sensors, modulating damp-
ers, 2-position valves, and HVAC equipment.
— Permits a maximum of 16 zones for heating only or
cooling only, or a maximum of 10 zones for heating
and cooling for each W180A Controller, depending
on the equipment used.
— Accommodates virtually any HVAC configuration
and provides the following zoned or individual room
temperature control:
• Damper zoning.
• Hydronic valve zoning.
• Equipment zoning.
• Combination of damper, hydronic valve, and equip-
ment zoning.
• Mixture of various HVAC systems.
— Does not require bypass dampers.
— Offers programmable HVAC equipment protection:
• Minimum air flow maintained via minimum duct
area(for dampered forced air systems with stan-
dard induction blower motors).
• Temperature setpoint limits (range boundaries).
• Damper position tracking (with optional end
switches and once-per-day position calibration).
• Minimum equipment off-time setting.
• Heat-to-cool switchover delay.
• Fan overrun periods.
The W180 System is customized for each specific appli-
cation using a Microsoft
®
Windows™-based PC setup
program.
NOTE: The W180 System air distribution algorithm adjusts
dampers to maintain a minimum airflow through each
piece of controlled equipment. This algorithm is de-
signed to work with all standard induction blower mo-
tors. If other blower motor types are used, alternate
bypass damper strategies must be used.
NOTE: When the W180 System is used in conventional
forced air systems, a return air temperature limit (for
example, T675A) is required as a backup for high tem-
perature limit.
See the Hardware Required section for a list of equip-
ment used in the W180 Zone Control System. For basic
information on HVAC systems, see Appendix C: HVAC
System Basics.
Fig. 1—W180 Zone Control System block
diagram.
W180A
CONTROLLER
S321
TOUCHPAD
PC FOR
CONFIGURATION
DAMPERS
VALVES
HVAC
EQUIPMENT
ROOM
SENSORS
OUTDOOR
SENSOR
HBUS
S321
TOUCHPAD
M5536C
HBUS
RS-232
HIGH LIMIT
CONTROLLER
HUMIDITY
SENSOR
Содержание W180
Страница 50: ...68 0139 50 W180 ZONE CONTROL SYSTEM ...