68-0139
24
W180 ZONE CONTROL SYSTEM
Fig. 19—Typical D635 damper wiring.
RLY 1
1/2 com
RLY 2
spare A
RLY 3
3/4 com
RLY 4
spare B
spare C
RLY 5
5/6 com
RLY 6
spare D
RLY 7
7/8 com
RLY 8
RELAY CONNECTIONS
GENERAL DAMPER WIRING NOTES:
1. CONNECT NO MORE THAN FOUR DAMPERS TO ONE RELAY PAIR.
2. DO NOT MIX DAMPER TYPES ON ONE RELAY PAIR.
3. CONNECT THE LAST DAMPER (MULTIPLE DAMPERS CONNECTED
TO ONE RELAY PAIR) AS SHOWN FOR THE RESPECTIVE DAMPER TYPE.
4. USE 24 VAC POWER SOURCE OTHER THAN THAT USED
FOR POWERING THE W180.
5. CONNECT DAMPER TO THE RELAY PAIR DESIGNATED THROUGH
SOFTWARE CONFIGURATION.
6. MAXIMUM DISTANCE FROM DAMPER TO CONTROLLER IS 1000 FT.
[300 M] USING 18 AWG SOLID OR STRANDED WIRE.
USE ADDITIONAL TRANSFORMERS
FOR DAMPERS. CALCUATE
TRANSFORMER SIZE NEEDED BY
ADDING 8.0 VA PER DAMPER.
1
2
3
X
4
5
6
Z
1
2
3
X
4
5
6
Z
1
2
3
X
4
5
6
Z
SINGLE AOBD
MULTIPLE AOBD
M8165A
Fig. 20—Typical Trol-A-Temp
®
damper wiring.
DETERMINE THE TEMPERATURE PROFILES
Determine and enter the Profile Name, Profile Start
Time, Days the profile is used, and desired heating and
cooling temperatures for each room in the house/building.
The example below shows a typical schedule for a house. A
profile:
— Can have different start times for different days of
the week.
— May be scheduled for only some days.
— May not have a start time at all.
Complete the Homeowner Lifestyle Worksheet in Ap-
pendix B for the customer. Use it when programming the
System.
RLY 1
1/2 com
RLY 2
spare A
RLY 3
3/4 com
RLY 4
spare B
spare C
RLY 5
5/6 com
RLY 6
spare D
RLY 7
7/8 com
RLY 8
RELAY CONNECTIONS
CW
COM
CCW
CW
COM
CCW
CW
COM
CCW
CW
COM
COM
COM
CCW
NC
NC
OPEN
CLOSE
D635
HONEYWELL D635
HONEYWELL D635
D635 W/END SWITCHES
END SWITCH
SET TO TRIP
AT FULLY
OPEN
POSITION
END SWITCH
SET TO TRIP
AT FULLY
CLOSED
POSITION
SINGLE D635
MULTIPLE D635
GENERAL DAMPER WIRING NOTES:
1. CONNECT NO MORE THAN FOUR DAMPERS TO ONE RELAY PAIR.
2. DO NOT MIX DAMPER TYPES ON ONE RELAY PAIR.
3. USE 24 VAC POWER SOURCE OTHER THAN THAT USED FOR POWERING THE W180.
4. CONNECT DAMPER TO THE RELAY PAIR DESIGNATED THROUGH SOFTWARE CONFIGURATION.
5. MAXIMUM DISTANCE FROM DAMPER TO CONTROLLER IS 1000 FT. [300 M] USING 18 AWG SOLID OR
STRANDED WIRE.
6. WHEN MORE THAN ONE WIRE MUST BE CONNECTED TO A TERMINAL, RUN A SHORT WIRE OUT FROM
THE TERMINAL AND CONNECT THE WIRES TO THE SHORT WIRE USING A WIRE NUT.
CW = OPEN
CCW = CLOSED
24 VAC
M7111A
USE ADDITIONAL TRANSFORMERS
FOR DAMPERS, CALCULATE
TRANSFORMER SIZE NEEDED
BY ADDING 2.2VA PER DAMPER.