11
68-0139
W180 ZONE CONTROL SYSTEM
Fig. 7—T7660A/T7660B Space Temperature Sensor dimensions in in. [mm].
COVER
MOUNTING
TABS
NO. 4-40 ALLEN
HD COVER
MOUNTING
SCREW (2)
15
16
[24]
1
[41]
5
8
2 [51]
2 [51]
3
1
4
[83]
2
1
4
[57]
1
1
[32]
1
8
[29]
1
4
3
1
4
[83]
M8157
1
1 LIGHTED BUTTON ON T7660B ONLY.
ELECTRICAL RATINGS:
Input Voltage: 24 Vac +20%/–30%, 50/60 Hz.
Power Consumption (Maximum) at 24 Vac: 2W, 85 mA,
2.2 VA.
TEMPERATURE RATINGS:
Ambient: 32
°
to 130
°
F [0
°
to 52
°
C].
Shipping and Operating: –20
°
to 130
°
F [–29
°
to 40
°
C].
HUMIDITY RATING: 5 to 95% RH, noncondensing.
DAMPER LEAKAGE: 1% nominal of flow.
DAMPER POSITION VERSUS FLOW RATE: See the
Specifications packed with the damper.
TORQUE RATINGS:
Running: 35 lb.-in. [4.0 N•m].
Breakaway: 35 lb.-in. [4.0 N•m].
Stall: 45 lb.-in.[5.0 N•m] minimum. 65 lb.-in. [7.4 N•m]
maximum.
MOTOR TIMINGS: 90 seconds for 90
°
stroke.
MATERIALS:
Damper Blade: 16 gauge corrosion resistant steel.
Blade Seal: Neoprene rubber with UL94HF1 rating.
Damper Shell: 24 gauge galvanized steel, 60 to 10 inch;
20 gauge galvanized steel, 12 to 16 inch.
DIMENSIONS:
Damper Portion: See Fig. 9.
Actuator: See Fig. 10.
APPROVALS:
Underwriter’s Laboratories Component Recognized:
File No. E4436, Guide No. XAPX.
CSA certified.
ACCESSORIES:
201052B Two Auxiliary Switches.
7640QW Metal Enclosure (to run conduit to actuator).
Fig. 8—C7600C Solid State Humidity Sensor
dimensions in in. [mm].
DAMPERS
D635 Zone Dampers
NOTE: If a custom-sized damper is required, it may be
used with an ML6161A1000 Direct Coupled Actuator
and be fully compatible with the W180 System.
MODELS: Includes ML6161A1000 Actuator (35 lb.-in.
torque, 90 second timing to control 90
°
dampers).
OS Number
Damper Diameter (Inches)
D635B1005
6
D635C1004
8
D635D1003
10
D635E1002
12
D635F1001
14
D635G1000
16
2
[70]
3
4
3
[80]
5
32
9
16
[14]
7
8
3 [96]
5
16
[8]
1[25]
7
32
[6]
M3129
Содержание W180