VISTA-128BPT/VISTA-250BPT Installation and Setup Guide
5-12
FIELD
TITLE and DATA ENTRIES
EXPLANATION
2
∗
∗
∗
∗
07
Auto-Disarm Delay (partition-
specific)
00
= no delay.
01-14
times 4 minutes (04-56) delay.
15
= no auto disarming.
This is the time between the end of the disarming window and the start of auto
disarming of the system.
2
∗
∗
∗
∗
08
Force Arm Enable for Auto-Arm
(partition-specific)
0
= disable
1
= enable
If enabled, the system automatically bypasses any faulted zones when it
attempts to auto-arm.
If disabled, the system will not auto-arm.
ULC
Force Arming is not a ULC Listed feature and
must be disabled for ULC installations.
2
∗
∗
∗
∗
09
Open/Close Reports by
Exception (partition-specific)
0
= disable
1
= enable
If enabled, Open/Close reports are sent
only if
the openings/closings occur
outside
the arm and disarm windows.
NOTES:
Open reports are also suppressed during the closing window in order to
prevent false alarms if the user arms the system, then re-enters the premises,
for example to retrieve a forgotten item.
Openings and closings are still recorded in the event log.
2
∗
∗
∗
∗
10
Allow Disarming Only During
Arm/Disarm Windows (partition-
specific)
0
= disable
1
= enable
If enabled, disarming of the system is allowed only during the
arming/disarming windows, or if the system is in alarm (if 2
∗
11 is set to 1).
NOTE:
This applies
only
to Operator-level users. Installer, Master, and
Manager-level users can disarm the system at any time.
NOTE:
Duress users behave the same way as Operator-level users.
2
∗
∗
∗
∗
11
Allow Disarm Outside Window if
Alarm Occurs
0
= disable
1
= enable
If enabled, allows the system to be disarmed outside the programmed disarm
(opening) window if an alarm has occurred. Otherwise disarming is allowed
only during the disarm window.
NOTE:
Used only if field 2
∗
10 is enabled.
2
∗
∗
∗
∗
18
Enable GOTO for this Partition
(partition-specific)
0
= disable
1
= enable
If enabled, this partition can be accessed from another partition’s keypad
using the GOTO command.
2
∗
∗
∗
∗
19
Use Partition Descriptor
0
= disable
1
= enable
If enabled, the normal keypad display will include a partition number and four-
digit descriptor.
2
∗
∗
∗
∗
22
Display Fire Alarms of Other
Partitions (partition-specific)
0
= disable
1
= enable
If enabled, allows fire alarms that occur on other partitions to be displayed at
this partition’s keypad(s).
2
∗
∗
∗
∗
23
Display Burg, Panic and CO
Alarms for Other Partitions
(partition-specific)
0
= disable
1
= enable
If enabled, allows burglary, panic and CO alarms that occur on other partitions
to be displayed at this partition’s keypad(s).
2
∗
∗
∗
∗
24
Display Troubles of Other
Partitions (partition-specific)
0
= disable
1
= enable
If enabled, allows troubles that occur on other partitions to be displayed at this
partition’s keypad(s).
Содержание VISTA-128BPT
Страница 2: ......
Страница 46: ......
Страница 56: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide 4 10 ...
Страница 88: ...V128BPT V250BPT Installation and Setup Guide 8 2 ...
Страница 104: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide C 2 ...
Страница 112: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Glossary 6 ...
Страница 118: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Index 6 ...
Страница 120: ...For the latest warranty information please go to www honeywell com security hsc resources wa ...
Страница 121: ...NOTES ...
Страница 122: ...NOTES ...
Страница 123: ...NOTES ...