Section 5 – Data Field Descriptions
5-7
FIELD
TITLE and DATA ENTRIES
EXPLANATION
1
∗
∗
∗
∗
20
Exit Error Logic Enable
0
= disable
1
= enable
Exit Error Logic functions as follows: the system at the end of the exit delay, if
a door is left open or an interior zone is faulted, starts the entry delay period,
and sounds the bell(s), siren(s), and keypad sounders for the duration of entry
delay. This gives the user time to re-enter the premises and disarm the
system before exit error occurs.
If the user does not re-enter the premises and disarm the system, the system
bypasses the faulted entry/exit and/or interior zone(s). The rest of the system
is armed. In addition, the following dialer reports are sent to the central
station if programmed:
Exit Error by Zone
Entry/Exit or Interior Alarm with the zone number
Bypass reports
NOTE:
This field has been eliminated in the Vista-128SIA software.
UL
Exit Error Logic is not suitable for use in a UL installation.
1
∗
∗
∗
∗
21
Exit Delay Reset
0
= disable
1
= enable
If enabled, when the panel is armed, the normal exit delay begins. After the
user exits, closes the door and then re-enters the premises, the exit delay
time is reset to the programmed value.
NOTES:
Exit Delay Reset is designed to allow an operator to re-enter the premises to
retrieve a forgotten item without triggering an alarm. This feature may only be
activated once after arming.
UL
Exit Delay Reset is not suitable for use in a UL installation.
Cross-Zoning
UL
Cross Zoning is not suitable for use in a UL installation.
Cross Zoning is designed so that a combination of two zones must be faulted within a 5-minute period of each other (once
the first zone trips, the cross zoning window begins, and when the 2nd zone trips within that window, the alarm for both
zones will occur). This prevents momentary faults from one of the zones from causing an alarm condition.
You can select four "sets" of cross-zones (programmed in data fields 1
∗
22, 1
∗
23, 1
∗
24 and 1
∗
25), keeping in mind the
following:
•
Both zones in each set must protect the same area.
•
When cross-zoning motion sensors, both device's areas of protection must be situated so that both units will trip at
the same time if their shared protected area is violated.
•
Both zones in each set must be in the same partition.
DO NOT cross-zone a fire zone with a burglary zone under any circumstance. DO NOT cross a fire zone with
another fire zone under any circumstance.
Conditions That Affect Cross-Zone Operation
•
If one of the zones in a pair is bypassed or has a zone response type set to 0, the cross-zoning feature does not apply.
•
If an entry/exit zone is paired with an interior follower zone, be sure to enter the entry/exit zone as the first zone of
the pair. This ensures that the entry delay time is started before the follower zone is processed.
•
If a relay is programmed to activate on a fault of one of the zones, the relay activates without the other zone being
faulted.
Содержание VISTA-128BPT
Страница 2: ......
Страница 46: ......
Страница 56: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide 4 10 ...
Страница 88: ...V128BPT V250BPT Installation and Setup Guide 8 2 ...
Страница 104: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide C 2 ...
Страница 112: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Glossary 6 ...
Страница 118: ...VISTA 128BPT VISTA 250BPT Installation and Setup Guide Index 6 ...
Страница 120: ...For the latest warranty information please go to www honeywell com security hsc resources wa ...
Страница 121: ...NOTES ...
Страница 122: ...NOTES ...
Страница 123: ...NOTES ...