6
OPERATION
92
RM640
www.honeywellprocess.com
34-VF-25-131 iss.1 GLO Feb 2019 US
C4.1.9.5
20mA Trimming Use this menu item if the current output of
the device is set to 20 mA, but the measured
loop current is not 20 mA. Enter the
measured value.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
0.0...25.0 mA
20 mA
C5 Communication
C5.1 HART
C5.1 HART
C5.1 HART
C5.1 HART
C5.1.1
Current Loop
Mode
Set this menu item to "On" if the "Primary
Variable" for current output 1 must also be
transmitted as a 4
…
20 mA signal. If this
menu item is set to "Off', this stops the
4
…
20 mA signal and starts HART
®
multi-
drop mode.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
On, Off
On
C5.1.2 Identification
C5.1.2.1
Polling Address
A polling address more than 0 will start
HART
®
multi-drop mode. If you start
HART
®
multi-drop mode, the current output
stays constant at 4 mA.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Operator
000...063
0
C5.1.2.2
Tag
Use this menu item to change the Tag name.
It can have a maximum of 8 characters. For
more data about the characters available,
refer to
Keypad functions
on page 71 (values
in menu items).
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Operator
—
TANK01
C5.1.2.3
Long Tag
Use this menu item to change the long Tag
name. It can have a maximum of 32
characters. For more data about the
characters available, refer to
Keypad
functions
on page 71 (values in menu items).
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Operator
—
—
C5.1.2.4
Manufacturer ID This is the manufacturer ID number given to
the supplier by the HART Foundation.
Read only
—
C5.1.2.5
Device Type
This is the device type number given to the
supplier by the HART Foundation.
Read only
—
C5.1.2.6
Device ID
This is the device ID number given to the
supplier by the HART Foundation. This
shows that the HART Foundation registered
the HART
®
device description (DD) file.
Read only
—
C5.1.2.7
Universal
Revision
This is the version of the HART protocol
used by the device.
Read only
—
C5.1.2.8
Device Revision
This is the revision number for the HART
®
device description.
Read only
—
C5.1.2.9
Software
Revision
This is the revision number for the device
software.
Read only
—
C5.1.2.10
Hardware
Revision
This is the revision number for the device
hardware.
Read only
—
Menu No. Function
Function description
Selection list
Default
Содержание RM640
Страница 4: ...4 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ABOUT THIS DOCUMENT RM640 ...
Страница 20: ...1 SAFETY INSTRUCTIONS 20 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 56: ...4 ELECTRICAL CONNECTIONS 56 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 120: ...6 OPERATION 120 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 164: ...9 DESCRIPTION OF HART INTERFACE 164 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 182: ...10 APPENDIX 182 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 183: ...APPENDIX 10 183 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...